OPERATING CONDITIONS
Road ONLY (2400 rpm)
Heating or Defrost mode
Run the unit on " HEAT or DEFROST " mode
Adjust the CPR to get the following gauge pressure values
STANDARD ADJUSTMENT
XARIOS 350 : 2,4 bars
(35 psig)
! Pressure value is given at the CPR port
!
CPR adjustment must be increased by :
0,1(bar) x D(m)
D : Evaporator location from the front of the box (in meter)
3 m
6 m
Carrier
T R A N S I C O L D
Standard
Standard + 0,6
Standard + 0,3