15

   
 
043 2 1.20 3.60 14.80
 2 1.20 3.60 14.80
 2 1.40 4.20 17.00
 2 2.47 7.42 30.00
101 2 2.60 7.64 31.00
111 2 3.04 9.13 37.00
121 2 3.54 10.62 43.00
141 2 3.54 10.62 43.00
 2 3.54 10.62 43.00
 2 4.00 12.00 48.00
 2 4.46 13.40 54.00
 2 5.04 15.14 61.00
280 2 5.62 16.88 68.00
* Based on a water velocity of 0.3 m/s in closed-loop and 0.9 m/s in open-loop
systems.
** Based on a water velocity of 3.6 m/s.

1 30HZ/HZV 043-052
2 30HZ/HZV 065
3 30HZ/HZV 091
4 30HZ/HZV 101
5 30HZ/HZV 111
6 30HZ/HZV 121-141
7 30HZ/HZV 161
8 30HZ/HZV 195
9 30HZ/HZV 225
10 30HZ/HZV 250
11 30HZ/HZV 280
Pressure drop, kPa
Water flow rate, l/s


CAUTION: To ensure correct operation of the units, these
restrictors must be installed. The restrictor is supplied with
the machine, inside the control box.
   
043 2 31 Condenser 09RS 022 circuit B - water outlet
 2 47 Condenser 09RS 054 - water outlet
111 2 47 Condenser 09RS 054 - water outlet
 2 47 Condenser 09RS 070 - water outlet
 2 56 Condenser 09RS 084 - water outlet