EasyManua.ls Logo

Carrier Pro-Dialog Plus 30HZV - Electrical Data

Carrier Pro-Dialog Plus 30HZV
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11

             

Nominal power supply V-ph-Hz 400-3-50
System voltage range V 360-440
 The control circuit is supplied via a factory-installed transformer.

30HZ kW 38.5 48.9 68 69 78 86 92 112 131 165 201 239 270
30HZV kW 38.5 48.6 65 70 77 86 94 112 135 165 200 234 266

30HZ A 63.8 81.1 112 114 129 142 152 185 217 273 333 396 448
30HZV A 63.8 80.6 108 116 127 142 156 185 224 273 332 388 441

30HZ - circuit A and B kW 45 55 77 82 90 100 109 132 155 194 232 - -
30HZ - circuit A kW - - - - - - - - - - - 155 155
30HZ - circuit B kW - - - - - - - - - - - 116 155
30HZV - circuit A and B kW 54 65 90 98 107 119 130 155 180 225 270 - -
30HZV - circuit A kW - - - - - - - - - - - 180 180
30HZV - circuit B kW - - - - - - - - - - - 135 180

30HZ - circuit A and B A 87 105 150 158 174 192 211 255 299 374 449 - -
30HZ - circuit A A - - - - - - - - - - - 299 299
30HZ - circuit B A - - - - - - - - - - - 224 299
30HZV - circuit A and B A 101 123 170 185 203 224 246 293 340 425 509 - -
30HZV - circuit A A - - - - - - - - - - - 340 340
30HZV - circuit B A - - - - - - - - - - - 255 340

30HZ - circuit A and B A 78 95 135 142 157 173 190 230 269 336 404 - -
30HZ - circuit A A - - - - - - - - - - - 269 269
30HZ - circuit B A - - - - - - - - - - - 202 269
30HZV - circuit A and B A 91 111 153 166 182 202 221 264 306 382 458 - -
30HZV - circuit A A - - - - - - - - - - - 306 306
30HZV - circuit B A - - - - - - - - - - - 229 306

30HZ - circuit A and B A 182 198 273 245 227 275 291 330 404 470 536 - -
30HZ - circuit A A - - - - - - - - - - - 404 404
30HZ - circuit B A - - - - - - - - - - - 338 404
30HZV - circuit A and B A 188 207 283 263 251 299 318 360 436 513 589 - -
30HZV - circuit A A - - - - - - - - - - - 436 436
30HZV - circuit B A - - - - - - - - - - - 360 436
 A 2.33 2.09 2.03 1.72 1.45 1.59 1.53 1.44 1.50 1.40 1.33 1.50 1.50
 A - - - - - - - - - - - 1.68 1.50
 A 2.06 1.87 1.85 1.58 1.37 1.48 1.44 1.37 1.43 1.34 1.28 1.43 1.43
 A - - - - - - - - - - - 1.57 1.43

30HZ - circuit A and B kA 15 15 15 15 20 20 20 20 20 25 25 - -
30HZ - circuit A kA - - - - - - - - - - - 25 25
30HZ - circuit B kA - - - - - - - - - - - 25 25
30HZV - circuit A and B kA 15 15 15 15 20 20 20 20 20 25 25 - -
30HZV - circuit A kA - - - - - - - - - - - 25 25
30HZV - circuit B kA - - - - - - - - - - - 25 25

Circuit A A 6 8 10 10 10 10 10 12 15 24 32 25 32
Circuit B A - - - - - - - - - - - 20 20
* Standard Eurovent conditions: Evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.3).
** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12°C, saturated condensing temperature (dew point) = 52°C
(30HZ)/66°C (30HZV), and a nominal voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor).
Current and power inputs not included in the values above.

30HZ/HZV 043 to 225 units have a single power connection point; 30HZ/HZV
250 to 280 units have two connection points.
The control box includes the following standard features:
- Starter and motor protection devices for each compressor
- Control devices

All connections to the system and the electrical installations must be in full
accordance with all applicable codes.
The Carrier 30HZ/HZV chillers are designed and built to ensure conformance
with local codes. The recommendations of European standard EN 60204-1
(corresponds to IEC 60204-1) (machine safety - electrical machine components
- part 1: general regulations) are specifically taken into account, when designing
the electrical equipment.

Conformance with EN 60204-1 is the best means of ensuring compliance with the
Machines Directive and § 1.5.1. Generally the recommendations of IEC 60364
are accepted as compliance with the requirements of the installation directives.
Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines.
1. The operating environment for the 30HZ/HZV chillers is specified below:
a. Environment* - Environment as classified in IEC 60364 § 3:
- ambient temperature range: +5°C to +40°C, class AA4
- humidity range (non-condensing)*: 50% relative humidity at 40°C,
90% relative humidity at 20°C
- altitude:≤2000m
- indoor installation*
- presence of water: class AD2* (possibility of water droplets)
- presence of hard solids, class AE2* (no significant dust present)
- presence of corrosive and polluting substances, class AF1 (negligible)
- vibration and shock, class AG2, AH2
b. Competence of personnel, class BA4* (trained personnel - IEC 60364)
2. Power supply frequency variation: ± 2 Hz.
3. The neutral (N) conductor must not be connected directly to the unit (if
necessary use a transformer).
4. Over-current protection of the power supply conductors is not provided with
the unit.
5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type
suitable for power interruption in accordance with EN 60947.
6. The units are designed for connection to TN networks (IEC 60364). For IT net-
works the earth connection must not be at the network earth. Provide a local earth,
consult competent local organisations to complete the electrical installation.



* The protection level required to conform to this class is IP21B (according to
reference document IEC 60529). All 30HZ/HZV units are protected to IP23C
and fulfil this protection condition.

Table of Contents

Related product manuals