EasyManua.ls Logo

Carrier WEATHERMAKER 39B - System Operation and Piping; Suction Piping Sizing and Pressure Loss; Expansion Valve Selection Criteria

Carrier WEATHERMAKER 39B
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
6
Refrigerant
Distributor
Nozzle
Orifice
Capacities
(Tons
of
Refrigeration)
NOZZLE
EVAPORATOR
TEMPERATURE
ORIFICE}
В-12
|
R-500
NUMBER
ыыы
шкы:
20Р
2
2:01
1.7
1.9]
1.6
2172
|25|21|
8|
40|
33|
28| 29|
24|
2.0
3
2.4
4
32
8$
|
5.0]
42]
3.5/8.0]
65] 55] 55|
46|
39
6
|
60]
5.0,
42]
95|
80]
6.5]
7.0]
6-0|
50
8
|
80|65|5.5[12
5[10.5|
85]
8.5|
70)
60
10
10.0]
8.0]
7.0]15.0]12.5]10.5]
11.0]
9.0]
7.5
12
112.0|10.0|
8.0
|18.5|15.0|]12
5]
13.5]
11.0]
9.5
15
|
15.0
17.0)
14
0]
11.5
17117.0|14.0|11
5
[26.0
|21.0|18.0|
19
0|
15.5]
13
0
20
^71200]116.5
[13.5
|31.0|25.0|21.0|
23.0]
19
015.5
25
{250/210
27
0128
0123
0|
19.0
30
[30.0
[25
0
[20.0
|45
0
[37.0 |31.0
|
33.0]
27.0
[23.0
35
|
35.0
[29
0
[24.0
[54
0
44
0137
0
39-0|32
0
[27.0
40
40
0
[33
0
|27.0
160
0
[49.0
|41
0]
44.0|36
0
[30.0
NOTES:
1
2.
2
Orifice
sizes
2-1/2,
3,
4,
5,
6
and
8
are
not
available
for
“А”
nozzles
Nozzle
designation
is
stamped
on
nozzle;
“G”
indicates
7/8
in.
ODM
distributor,
Е”
indicates
1-1/8
in.
ODM
distributor,
"С”
indicates
1-3/8
in.
ODM
distributor,
"A''
indicates
1-5/8
in.
ODM
distributor.
Therefore,
only
the
nozzles
having
the
same
letter
are
physically
interchangeable.
c.
Standard
coils
above
size
080
are
face
split
with
the
load
for
each
coil
divided
evenly
between
the
two
or
three
distributors.
Unit
sizes
130,
135
and
140
contain
two
coils,
each
of
which
are
face
split.
The
percentage
of
total
unit
load
handled
by
each
distrib-
utor
is
as
follows:
(1)
Unit
sizes
040
thru
080:
10096
(2)
Unit
sizes
090
thru
120:
50%
8-row
coil
on
120
(3)
Unit
size
120
with
8-row
coil:
33-1/3%
(4)
Unit
size
130:
25%
(5)
Unit
size
135:
2346
for
each
distributor
of
the
smaller
coil
and
2796
for
each
distributor
of
the
larger
coil.
(6)Unit
size
140
with
4-
and
6-row
coil:
20%
each
distributor
of
smaller
coil;
30%
each
distributor
of
larger
coil.
(7)
Unit
size
140
with
8-row
coil:
20%
each
distributor
of
both
coils.
except
.
Factory-installed
nozzle
should
be
replaced
if
the
following
relationship
is
not
met:
design
load
(per
distributor)
nozzle
orifice
capacity
(Table
6)
.
If
two
nozzles
satisfy
above
relationship,
choose
the
smaller.
=
0.90
to
1.20
.
Mark
final
nozzle
size,
where
indicated,
on
unit
label
for
future
reference.
This
will
show
nozzle
size
has
been
checked.
Partial
Load
Operation
System
controls
must
be
designed
with
consideration
of
following:
1.
Мо
coil
or
coil
split
served
by
a
single
refrig-
erant
distributor
and
expansion
valve
can
be
expected
to
operate
satisfactorily
at
less
than
50%
of
design
load.
.
As
load
reduces,
a
portion
of
coil
surface
must
be
deactivated
so
that
remaining
active
coil
or
coil
splits
operate
between
50
and
100%
of
design
load.
.
Face-split
coils
may
be
used
when
air
quantity
is
constant.
In
variable
volume
systems,
row-
split
coils
must
be
used.
If
operation
must
be
below
50%
of
design
load,
hot
gas
bypass
must
be
used.
Refer
to
Carrier
System
Design
Manual
for
details.
Suction
Piping
IL
2.
Connect
suction
piping
per
Fig.
14,
15
and
16.
Suction
line
from
evaporator
to
end
of
15
diameter
long
riser
(located
between
reducer
fittings)
must
be
sized
for
high
velocity.
Refer
to
Carrier
System
Design
Manual,
Part
3
for
suction
pipe
sizing
charts.
This
piping
length
will
normally
result
in
an
equivalent
length
of
20
ft
and
should
be
sized
for
a
pressure
loss
corresponding
to
0.5
F.
Remaining
suction
line
should
be
sized
for
a
pressure
drop
correspond-
ing
to
1.5
F
for
a
total
suction
line
pressure
drop
corresponding
to
2
F.
.
Suction
risers
must
be
sized
to
provide
ade-
quate
oil
return
at
minimum
load.
When
a
suction
riser
is
designed
to
permit
oil
return
at
minimum
load,
the
pressure
drop
at
full
load
may
be
too
great.
If
this
situation
occurs,
a
double
suction
riser
should
be
used.
Refer
to
Carrier
System
Design
Manual
for
details
of
sizing.
Expansion
Valve
(field-supplied)
1.
Expansion
valve
must
satisfy
following:
a.
Design
load
per
distributor.
b.
Available
pressure
drop.
c.
Valve
inlet
temperature (condensing
tem-
perature
minus
subcooling).
d.
Design
evaporator
temperature.
e.
Valve
must
have
non-condensing
charge
power
element.
f.
If
selection
falls
between
two
valves,
choose
smaller.
.
Install
expansion
valve(s).
Refer
to
Fig.
14,
15
and
16
for
proper
location
of
sensing
bulb
and
equalizer
connection.
.
Install
condensate
pan(s)
under
expansion
valve(s)
per
Fig.
17.

Other manuals for Carrier WEATHERMAKER 39B

Related product manuals