APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ 10 to 245 dF SPLO 60 78,108
SP.H.O SPT hi alert limit/occ 10 to 245 dF SPHO 85 78,108
SP.L.U SPT lo alert limit/unocc –10 to 245 dF SPLU 45 78,108
SP.H.U SPT hi alert limit/unocc –10 to 245 dF SPHU 100 78,108
SA.L.O EDT lo alert limit/occ –40 to 245 dF SALO 40 78,108
SA.H.O EDT hi alert limit/occ –40 to 245 dF SAHO 100 78,108
SA.L.U EDT lo alert limit/unocc –40 to 245 dF SALU 40 78,108
SA.H.U EDT hi alert limit/unocc –40 to 245 dF SAHU 100 78,108
RA.L.O RAT lo alert limit/occ –40 to 245 dF RALO 60 78,108
RA.H.O RAT hi alert limit/occ –40 to 245 dF RAHO 90 78,108
RA.L.U RAT lo alert limit/unocc –40 to 245 dF RALU 40 78,108
RA.H.U RAT hi alert limit/unocc –40 to 245 dF RAHU 100 78,108
R.RH.L RARH low alert limit 0 to 100 % RRHL 0 78,108
R.RH.H RARH high alert limit 0 to 100 % RRHH 100 78,108
SP.L SP low alert limit 0 to 5 " H2O SPL 0 78,108
SP.H SP high alert limit 0 to 5 " H2O SPH 2 78,108
BP.L BP lo alert limit –0.25 to 0.25 " H2O BPL -0.25 78,79,108
BP.H BP high alert limit 0.25 to 0.25 " H2O BPH 0.25 78,79,108
IAQ.H IAQ high alert limit 0 to 5000 IAQH 1200 78,79,108
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim –10 to 10 ^F SAT_TRIM 0 79
RAT.T RAT Trim –10 to 10 ^F RAT_TRIM 0 79
OAT.T OAT Trim 10 to 10 ^F OAT_TRIM 0 79
SPT.T SPT Trim –10 to 10 ^F SPT_TRIM 0 79
CTA.T Cir A Sat.Cond.Temp Trim 30 to 30 ^F SCTATRIM 0 79
CTB.T Cir B Sat.Cond.Temp Trim 30 to 30 ^F SCTBTRIM 0 79
SP.A.T Suct.Press.Circ.A Trim –50 to 50 PSIG SPA_TRIM 0 79
SP.B.T Suct.Press.Circ.B Trim –50 to 50 PSIG SPB_TRIM 0 79
DP.A.T Dis.Press.Circ.A Trim –50 to 50 PSIG DPA_TRIM 0 79
DP.B.T Dis.Press.Circ.B Trim –50 to 50 PSIG DPB_TRIM 0 79
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open 79,80
IGC.L IGC Feedback - Off Open/Close GASFANLG Open 79,80
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 25,80
ECS.L Economizer Switch - No Open/Close ECOSWLOG Open 80
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open 80
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 26,80
DL2.L Dmd.Lmt.Sw.2 - Dehumid - Off Open/Close DMD_SW2L Open 26,80
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open 26,80
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open 80,108
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open 80
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open 80
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open 80
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF TEST Off 80,81
METR Metric Display ON/OFF DISPUNIT Off 80,81
LANG Language Selection 0 to 1(multi-text strings) LANGUAGE 0 80,81
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable 80,81
PASS
Service Password 0000 to 9999 PASSWORD 1111 80,81