EasyManua.ls Logo

Carrier WEATHERMAKER 50A3050 - Page 193

Carrier WEATHERMAKER 50A3050
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
193
LOCAL SCHEDULE R
"0=OFF
1=ON"
schedule_1 BV:5
MIXED AIR TEMPERATURE F ma_temp_1 AV:1500
OAQ - PPM OUTDOOR CO2 R/W no unit 0 to 5000 oaq_1 AV:113
OCCUPIED COOL MODE END F occl_end_1 AV:114
OCCUPIED COOL MODE START F occlstrt_1 AV:115
OCCUPIED HEAT MODE END F ocht_end_1 AV:116
OCCUPIED HEAT MODE START F ochtstrt_1 AV:117
OCCUPIED? R/W
"0=NO
1=YES"
occ_status_1 BV:2008
OUTSIDE AIR RELATIVE HUMIDITY R/W % 0 to 100 oarh_1 AV:119
OUTSIDE AIR TEMPERATURE R/W °F -40 to 240 oat_1 AV:1003
POWER EXHAUST RELAY A R
"0=OFF
1=ON"
pe_a_1 BV:72
POWER EXHAUST RELAY B R
"0=OFF
1=ON"
pe_b_1 BV:73
POWER EXHAUST RELAY C R
"0=OFF
1=ON"
pe_c_1 BV:74
RELAY 3 W1 GAS VALVE 2 R
"0=OFF
1=ON"
hs3_1 BV:76
RELAY 4 W2 GAS VALVE 2 R
"0=OFF
1=ON"
hs4_1 BV:77
RELAY 5 W1 GAS VALVE 3 R
"0=OFF
1=ON"
hs5_1 BV:78
RELAY 6 W2 GAS VALVE 3 R
"0=OFF
1=ON"
hs6_1 BV:79
REQUESTED HEAT STAGE R no unit heat_run_1 AV:2003
RETURN AIR RELATIVE HUMIDITY R/W % 0 to 100 rarh_1 AV:134
RETURN AIR TEMPERATURE R/W °F -40 to 240 rat_1 AV:135
SPACE TEMP OFFSET RANGE R/W °^F 1 to 10 spto_rng_1 AV:139
SPACE TEMPERATURE R/W °F -40 to 240 spt_1 AV:137
STAGED GAS LAT 1 F lat1sgas_1 AV:150
STAGED GAS LAT 2 F lat2sgas_1 AV:151
STAGED GAS LAT 3 F lat3sgas_1 AV:152
STATIC PRESSURE RH2O static_press_1 AV:1016
STATIC PRESSURE RESET R/W no unit 0 to 15 spreset_1 AV:157
STATIC PRESSURE SETPOINT R/W H2O
0 to 5 sa_static_stpt_1 AV:3050
SUPPLY AIR RESET R
"0=OFF
1=ON"
modesars_1 BV:93
SUPPLY AIR SETPNT. RESET R/W °^F 0 to 20 sasprset_1 AV:158
SUPPLY AIR SETPOINT R/W °F 45 to 75 sa_temp_stpt_1 AV:3007
SUPPLY FAN RELAY R
"0=OFF
1=ON"
sfan_rly_1 BV:94
SUPPLY FAN STATUS SWITCH R/W
"0=OFF
1=ON"
sfs_1 BV:95
SUPPLY FAN VFD SPEED R% 0 to 100 sf_vfd_output_1 AV:2050
SYSTEM COOLING DEMAND LEVEL R no unit cool_demand_level_1 AV:9006
SYSTEM DEMAND LIMITING R
"0=INACTIVE
1=ACTIVE"
dem_lmt_act_1 BV:3
SYSTEM HEATING DEMAND LEVEL R no unit heat_demand_level_1 AV:9036
SYSTEM OAT MASTER F mstr_oa_temp_1 AV:80001
THERMOSTAT G INPUT R/W
"0=OFF
1=ON"
g_input_1 BV:1021
THERMOSTAT W1 INPUT R/W
"0=OFF
1=ON"
w1_input_1 BV:1019
THERMOSTAT W2 INPUT R/W
"0=OFF
1=ON"
w2_input_1 BV:1020
THERMOSTAT Y1 INPUT R/W
"0=OFF
1=ON"
y1_input_1 BV:1017
THERMOSTAT Y2 INPUT R/W
"0=OFF
1=ON"
y2_input_1 BV:1018
UNOCCUPIED COOL MODE END F uccl_end_1 AV:168
UNOCCUPIED COOL MODE START F ucclstrt_1 AV:169
UNOCCUPIED HEAT MODE END F ucht_end_1 AV:170
UNOCCUPIED HEAT MODE START R °F uchtstrt_1 AV:171
VENT REHEAT RAT OFFSET R/W °^F 0 to 8 dhvraoff_1 AV:183
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (CONT)
NAME READ/WRITE UNITS RANGE OBJECT NAME OBJECT ID

Table of Contents