202
APPENDIX F — OPTIONAL FACTORY-INSTALLED LOW AMBIENT MOTORMASTER
®
V CONTROL (cont)
4. Restore factory defaults by changing the value in P48 using
UP and DOWN buttons and then storing the value by press-
ing MODE.
5. Press MODE again to re-display the value of P48.
6. Change the value of P48 to the desired factory default mode
using UP and DOWN buttons then press MODE. The Mo-
tormaster V control is now restored to factory settings.
Fig. Q — Low Ambient Motormaster V Wiring (48/50A020-060 Units Shown)