ITEM EXPANSION RANGE DEFAULT ENTRY
COOL (cont) COOLING CONFIGURATION
A1.EN Enable Compressor A1 Enable/Disable Enable
A2.EN Enable Compressor A2 Enable/Disable Enable
B1.EN Enable Compressor B1 Enable/Disable Enable
B2.EN Enable Compressor B2 Enable/Disable Enable
CS.A1 CSB A1 Feedback Alarm Enable/Disable Enable
CS.A2 CSB A2 Feedback Alarm Enable/Disable Enable
CS.B1 CSB B1 Feedback Alarm Enable/Disable Enable
CS.B2 CSB B2 Feedback Alarm Enable/Disable Enable
REV.R Rev. Rotation Verified? Yes/No No
H.SST Hi SST Alert Delay Time 5 -30 min 10
OV.DB Outdoor VFD SCT DeadBand 0 to 20 2
OV.RH Outdoor VFD Dehum-RH SPD 0 to 100 50
LA.ST OV MinStartSpeed Low Amb 0 to 100 12
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF EDT Reset Configuration 0 to 3 (multi-text strings) 0
RTIO Reset Ratio 0 to 10 2
LIMT Reset Limit 0 to 20 ^F 10
RES.S EDT 4-20 ma Reset Input Enable/Disable Disable
HEAT HEATING CONFIGURATION
HT.CF Heating Control Type 0 to 4 0
HT.SP Heating Supply Air Setpt 80 to 120 dF 85
OC.EN Occupied Heating Enabled Yes/No No
LAT.M MBB Sensor Heat Relocate Yes/No No
G.FOD Fan-Off Delay, Gas Heat 45-600 45
E.FOD Fan-Off Delay, Elec Heat 10 to 600 30
SG.CF STAGED GAS CONFIGS
HT.ST Staged Gas Heat Type 0 to 4 0
CAP.M Max Cap Change per Cycle 5 to 45 45
M.R.DB S.Gas DB min.dF/PID Rate 0 to 5 0.5
S.G.DB St.Gas Temp. Dead Band 0 to 5 ^F 2
RISE Heat Rise dF/sec Clamp 0.05 to 0.2 0.06
LAT.L LAT Limit Config 0 to 20 ^F 10
LIM.M Limit Switch Monitoring? Yes/No No
SW.H.T Limit Switch High Temp 110 to 180 dF 170
SW.L.T Limit Switch Low Temp 100 to 170 dF 160
HT.P Heat Control Prop. Gain 0 to 1.5 1
HT.D Heat Control Derv. Gain 0 to 1.5 1
HT.TM Heat PID Rate Config 60 to 300 sec 90
SP SUPPLY STATIC PRESS.CFG.
SP.CF Static Pressure Config 0 to 1 (multi-text strings) No
CV.FD Constant Vol IDF is VFD? Yes/No No
SP.FN Static Pres.Fan Control? Yes Yes
SP.S Static Pressure Sensor Enable/Disable Disable
SP.LO Static Press. Low Range -10 to 0 0
SP.HI Static Press. High Range 0 to 10 5
SP.SP Static Pressure Setpoint 0 to 5 " H2O 1.5
SP.MN VFD Minimum Speed 0 to 100 % 20
SP.MX VFD Maximum Speed 0 to 100 % 100
SP.FS VFD Fire Speed Override 0 to 100 % 100
HT.VM VFD Heating Min Speed 75 to 100 % 75
SP.RS Stat. Pres. Reset Config 0 to 4 (multi-text strings) 0
SP.RT SP Reset Ratio (/dF) 0 to 2.00 in. wg/dF 0.2
SP.LM SP Reset Limit in iwc () 0 to 2.00 in. wg 0.75
SP.EC SP Reset Econo. Position 0 to 100 % 5
S.PID STAT.PRESS.PID CONFIGS
SP.TM Stat.Pres.PID Run Rate 1 to 200 sec 2
SP.P Static Press. Prop. Gain 0 to 100 20