Technical CATERPILLAR – 1000 kVA Page
33
Description UTILITY POWER MODULE
Revision 1.0 1 May 2006
6. Switchgear & Controls
6.1 CONTROL SYSTEM DESCRIPTION
Utility paralleling switchgear is intended for automatic or manual synchronizing with a
utility power source as a load management system, with provisions for standby
operation feeding an isolated load network. Modes of operation are field configurable
and include:
- Single Unit Island Mode.
- Multiple Unit Island Mode (up to 18 units).
o Includes Load Sense / Load Demand control, ramp loading, bumpless transfer
o Load sharing (kW and kVAR) capability is provided via network communication.
- Single Unit Utility Parallel Mode.
o Automatic paralleling.
o Selectable for Import / Export control. (Requires 4-20 mA customer input.)
o This product is intended for unmanned operation Automatic paralleling.
.Convenient operator interface
- 4 lines text display
- Graphical one-line diagrams with LED status indicators.
Modules can operate in groups up to 18 with all communications synchronizing and
load sharing between units by datalink for quick and convenient setup. (Max
cumulative distance 450 m)
Protection includes 1600A motorized generator 3 poles circuit breaker with 55kA
interrupt capability, extensive protective relays and internal power distribution.
Convenient customer connections for power
Request to run / stop signal (customer input)
Can also be paralleled to Woodward compatible legacy modules in island operation.
Languages available: Dutch, German, French, Russian, Spanish.