Application and Installation Guide EMCP 4 SCADA Data Links
©2013 Caterpillar
All rights reserved. Page 19
CURRENT (AMPS) DATA
Generator Average AC RMS Current (101)
Generator Phase A AC RMS Current (111)
Generator Phase B AC RMS Current (112)
Generator Phase C AC RMS Current (113)
Generator Total Percent Current (174) – sum of phase currents, as a percent of generator rated
current, calculated from Generator Rated Voltage (setpoint) and Generator Rated Power
(setpoint)
FREQUENCY DATA
Generator Average AC RMS Frequency (102)
Generator Average AC RMS Frequency Percent (183)
5.2 GENERATOR POWER MONITORING
REAL POWER DATA
Generator Total Percent Real Power (105) – percent of Generator Rated Power (setpoint)
Generator Total Real Power (106)
Generator Phase A Real Power (117)
Generator Phase B Real Power (119)
Generator Phase C Real Power (121)
APPARENT POWER DATA
Generator Phase A Apparent Power (123)
Generator Phase B Apparent Power (125)
Generator Phase C Apparent Power (127)
Generator Total Apparent Power (138)
Generator Total Percent Apparent Power (140) – percent of Generator Rated Apparent Power
(setpoint)
REACTIVE POWER DATA
Generator Phase A Reactive Power (129)
Generator Phase B Reactive Power (131)
Generator Phase C Reactive Power (133)
Generator Total Reactive Power (141)
Generator Total Percent Reactive Power (143) – percent of generator rated reactive power,
calculated from Generator Rated Power (setpoint) and Generator Rated Apparent Power
(setpoint)
POWER FACTOR DATA
Generator Overall Power Factor (103) – Chapter 7 for a programming example
Generator Overall Power Factor Lagging (104) – indicates overall lead/lag status
Generator Phase A Power Factor (135)
Generator Phase B Power Factor (136)
Generator Phase C Power Factor (137)
Generator Phase A Power Factor Lagging (159) – indicates phase lead/lag status
Generator Phase B Power Factor Lagging (160) – indicates phase lead/lag status