Application and Installation Guide EMCP 4 SCADA Data Links
©2013 Caterpillar
All rights reserved. Page 20
Generator Phase C Power Factor Lagging (161) – indicates phase lead/lag status
5.3 GENERATOR OTHER MONITORING
Most of these monitoring parameters are only available if they are being received over either the Primary
or Accessory Data Link (typically from either the RTD module or the Thermocouple module). Excitation
data would be coming from a CDVR module.
Generator Front Bearing Temperature from Data Link (149) – also called bearing #2 or right bearing
Generator Rear Bearing Temperature from Data Link (150) – also called bearing #1 or left bearing
Generator Phase A Winding Temperature from Data Link (151)
Generator Phase B Winding Temperature from Data Link (152)
Generator Phase C Winding Temperature from Data Link (153)
Generator Rear Bearing Temperature from I/O Pin (162) – for legacy use only
Battery Voltage (202) – measured at the input to the EMCP 4, which may be lower than the
voltage at the battery terminals; see Chapter 7 for reading example
Generator Excitation Field Voltage from Data Link (338)
Generator Excitation Field Current from Data Link (340)
5.4 BUS AC MONITORING
Bus AC Monitoring is only available on the EMCP 4.4.
VOLTAGE DATA
Bus Average Line-Line AC RMS Voltage (164)
Bus Phase A Line-Line AC RMS Voltage (166)
Bus Phase B Line-Line AC RMS Voltage (167)
Bus Phase C Line-Line AC RMS Voltage (168)
Bus Phase A Line-Neutral AC RMS Voltage (169)
Bus Phase B Line-Neutral AC RMS Voltage (170)
Bus Phase C Line-Neutral AC RMS Voltage (171)
Bus Average Line-Neutral AC RMS Voltage (172)
Bus Average Line-Line AC RMS Voltage Percent (173) – percentage of generator rated voltage
FREQUENCY DATA
Bus Average AC RMS Frequency (165)
5.5 GENERATOR SET STATE MONITORING AND CONTROL
START / STOP CONTROL
Automatic Start/Stop State (206) – engine operation state
Bypass Cooldown (300) – command
Engine Control Switch Position (301)
Engine Control Switch Command (302)
Auto Start/Stop Fuel Control Enabled (307) – status
Dedicated Digital Input #1 (E-Stop) Active Status (612)
Dedicated Digital Input #2 (Initiate Command) Active Status (613)
Cooldown Duration Remaining (1054) – cooldown timer; only valid while engine is in cooldown
Remote Initiate Command (1055) – when ECS is in Auto position, sending True commands the
engine to start.