Application and Installation Guide EMCP 4 SCADA Data Links
©2013 Caterpillar
All rights reserved. Page 31
CRANK/START COUNTERS
The EMCP 4 provides service-related information such as the number of crank and start attempts and
successes.
Number of Crank Attempts (213)
Number of Successful Starts (215)
5.9 PROGRAMMABLE CYCLE TIMERS
Programmable Cycle Timer 1 Output 3 Status (1487)
Programmable Cycle Timer 2 Output 3 Status (1488)
Programmable Cycle Timer 3 Output 3 Status (1489)
Programmable Cycle Timer 4 Output 3 Status (1490)
Programmable Cycle Timer 5 Output 3 Status (1491)
Programmable Cycle Timer 6 Output 3 Status (1492)
Programmable Cycle Timer 7 Output 3 Status (1493)
Programmable Cycle Timer 1 Output 1 Status (2060)
Programmable Cycle Timer 2 Output 1 Status (2061)
Programmable Cycle Timer 3 Output 1 Status (2062)
Programmable Cycle Timer 4 Output 1 Status (2063)
Programmable Cycle Timer 5 Output 1 Status (2064)
Programmable Cycle Timer 6 Output 1 Status (2065)
Programmable Cycle Timer 7 Output 1 Status (2066)
Programmable Cycle Timer 1 Output 2 Status (2067)
Programmable Cycle Timer 2 Output 2 Status (2068)
Programmable Cycle Timer 3 Output 2 Status (2069)
Programmable Cycle Timer 4 Output 2 Status (2070)
Programmable Cycle Timer 5 Output 2 Status (2071)
Programmable Cycle Timer 6 Output 2 Status (2072)
Programmable Cycle Timer 7 Output 2 Status (2073)
5.10 SYSTEM INFORMATION
MODULE INSTALLATION INFO
Genset Control Online (1090) – this refers to the EMCP 4 GSC, and will always return True
Engine Control Online (1091) – this refers to the ADEM engine ECM, and will return True only if
the ADEM supports CAN communications
Secondary Engine Control Online (1092)
External I/O #1 Online (1093) – this refers to a Discrete I/O module configured for Instance #1
External I/O #2 Online (1094) – this refers to a Discrete I/O module configured for Instance #2
External I/O #3 Online (1095) – this refers to a Discrete I/O module configured for Instance #3
External I/O #4 Online (1096) – this refers to a Discrete I/O module configured for Instance #4
Digital AVR Online (1097) – this refers to a CDVR module
RTD Module Online (1098)
Thermocouple #1 Online (1099) – this refers to a Thermocouple module on the Accessory Data Link
Thermocouple #2 Online (1100) – this refers to a Thermocouple module on the Primary Data Link
SCR Module Online (1103) – this refers to an SCR (aftertreatment control) module
NETWORK STATUS
These registers indicate the fault status (ok or fault) of the associated networks.