Application and Installation Guide EMCP 4 SCADA Data Links
©2013 Caterpillar
All rights reserved. Page 32
Primary Data Link Status (1140)
Accessory Data Link Status (1141)
RS-485 SCADA Data Link Status (1142)
TCP/IP SCADA Data Link Status (1143)
RS-485 Annunciator Data Link Status (1144)
CDL Data Link Status (1145)
OTHER
Lamp Test Command (303) – write True to begin lamp test, False to cancel
Control Serial Number (1276) – reads the serial number of the EMCP 4 GSC; this is the number
printed on the back cover of the module; see Chapter 7 for reading example
Software Build Version (2188)
5.11 EMCP 4 GSC INPUTS AND OUTPUTS
ANALOG INPUTS
An example of reading and interpreting analog inputs is provided in Chapter 7.
Spare Analog Input Percent (207) – for legacy purposes only; this will always read 0xFFFF; for
new applications, use other percent registers
Spare Analog Input Temperature (208) – for legacy purposes only; reads the temperature
associated with analog input #3; for new applications, use other temperature registers
Spare Analog Input Pressure (209) – for legacy purposes only; reads the pressure associated
with analog input #3; for new applications, use other pressure registers
Analog Input #1 Sensor Value (648) – sensor reading in , V, %, or mA units
Analog Input #2 Sensor Value (649) – sensor reading in , V, %, or mA units
Analog Input #3 Sensor Value (650) – sensor reading in , V, %, or mA units
Analog Input #4 Sensor Value (651) – sensor reading in , V, %, or mA units
Analog Input #1 Data Value (652) – converted data value, in Data Identification (setpoint) units
Analog Input #2 Data Value (654) – converted data value, in Data Identification (setpoint) units
Analog Input #3 Data Value (656) – converted data value, in Data Identification (setpoint) units
Analog Input #4 Data Value (658) – converted data value, in Data Identification (setpoint) units
ANALOG OUTPUTS (EMCP 4.3 AND 4.4)
Analog outputs are supported on EMCP 4.3 and 4.4. An example of interpreting and writing analog
outputs is provided in Chapter 7
Analog Output #1 Data Value (660) – assigned data value, in Output Type (setpoint) units
Analog Output #2 Data Value (662) – assigned data value, in Output Type (setpoint) units
Analog Output #3 Data Value (664) – assigned data value, in Output Type (setpoint) units
Analog Output #1 Data Command (681) – output pin reading in , V, or mA units
Analog Output #2 Data Command (683) – output pin reading in , V, or mA units
Analog Output #3 Data Command (685) – output pin reading in , V, or mA units
DIGITAL INPUTS
These registers indicate whether the input pin is active or not. The EMCP 4.2 only has 6 digital inputs.
The rest are supported by EMCP 4.3 and 4.4 only.
Digital Input #1 Active Status (600)