ENGLISH
Mainsinputvoltage
Max.power
Chargecurrent
-nominal
-arithmetic
Currentcontrol
Consumption(noconnectedmains)
Automaticcontrolofchargecycles
-Maxcharge
-Maintenance
Commutatorforbatterychoice(PborGel)
Lengthof14,4Vend-chargephase
-Leadtypebattery
-Standingtypebattery
Overloadprotected
Overtemperatureprotected
Inversionpolarityprotection
Securityon/offswitch
12Vfuse
230Vfuse
ChargesignalledbyLED
230Vconnection
Batteryconnection
Mainssignalconnection
Dimensions(mm)
Weight(Kg)
Alwaysprovided
230Vac50Hz/12Vdc
180VA
A915
15 A
13 A
0,3mA
25°C
14,4V
13,8V
Terminals6,3
Terminals6,3
cartype20A
internal3,15A
160x200H105
3,8
20min.
380min.
Schukoplug
Anodizedaluminiumcase
Chargesystem
Bufferbattery
SPECIFICATIONS
5
IMPORTANT: -Theinstallationofthisdevicemustbecarriedoutbyspecializedtechnicians.
-Incaseofbatterycharger’smisuse,theguaranteefallsoffandthemanufacturer
declinesallresponsibilityfordamagestopeopleandthings.
-Donotcarryoutanymaintenancewhenthebatterychargerisconnectedtothe
230Vpowersupplynet.
BATTERY CHARGER
- Installthebatterychargerinadedicatedroom,dryandventilated;fixitinaproperway.
- Donotcoverairintakesandassureanappropriateventilation.
- Beforedisconnectingthebatterychargerfrom230Vpowersupply,turnthesecurityswitchoff.
CABLES
- Usecableswithappropriatesection,minimumcrosssectionarea4mm².
- Protectcablesfromanypossibledamage.
ADVICEANDCHECKS