FORCECLIMA 7400 SOUNDLESS TOUCHFORCECLIMA 7400 SOUNDLESS TOUCH
6968
ENGLISH ENGLISH
-
-
-
D. Pump the cooling system, if possible.
E. If vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
F. Ensure that the cylinder is positioned on the scale before recovery takes place.
G. Switch on the recovery machine and operate it according to the manufacturer’s instructions.
H.
I. Do not exceed the maximum working pressure of the cylinder, even temporarily.
J.
isolation valves are closed.
K. Recovered refrigerant must not be charged to another refrigeration system, unless
cleaned and checked.
10. Labelling
of refrigerant. The labelling must be dated and signed. Ensure that there are labels on the
11. Recovery
- When refrigerant is removed from a system, either for service or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
- When transferring refrigerant to cylinders, ensure that only suitable refrigerant-recovery
cylinders are used. Ensure that the correct number of cylinders is available to support
the total load of the system. All cylinders to be used are designated for the refrigerant
in good working order. Empty recovery cylinders are evacuated and, if possible, cooled
before recovery takes place.
-
addition, a set of calibrated weighing scales must be available and in good working order.
Hoses must be complete with disconnect couplings free of leakage and in good running
order. Before using the recovery machine, check that it is in good running order, properly
maintained, and that all associated electrical components are sealed to prevent ignition in
the event of refrigerant release. Consult the manufacturer in case of doubt.
-
recovery cylinder, and the applicable waste transfer note must be provided. Do not mix
refrigerants in recovery units and especially not in cylinders.
2. Purge the circuit with inert gas.
3. Evacuate.
4. Purge again with inert gas.
5. Open the circuit by cutting or brazing.
- The refrigerant charge must be recovered from the correct recovery cylinders. The system
to be repeated several times. Oxygen or compressed air must not be used for the task.
- Cleanliness must be achieved by breaking the vacuum in the system with oxygen-
is no refrigerant left in the system. When using the oxygen-free nitrogen end-charge,
the system must be vented to atmospheric pressure to allow for work. This operation is
absolutely vital if brazing operations are to take place on pipes.
- Ensure that the vacuum pump outlet is not near any source of ignition and that ventilation
is available.
8. Loading procedure
-
refrigerant contained in them.
- Cylinders must be kept in an upright position.
- Ensure that the refrigeration system is grounded before loading the system with
refrigerant.
-
-
Before reloading, the system must be pressure-tested with oxygen-free nitrogen. The system
leakage test must be carried out before leaving the site.
9. Commissioning
Before carrying out this procedure, it is essential that the technician is thoroughly familiar with
safely recovered. Before the task is carried out, a sample of oil and refrigerant should be taken
be power before starting with the task.
A.
B. Electrically isolate the system.
C. Before attempting the procedure, ensure that
-