18
V8.18
Power Supply Requirements
EVAPORATOR CONDENSING UNIT
SPLIT
SYSTEM
FAN AMPS
115V/60HZ POWER INPUT WATTS
UNIT AMPS
115V/60HZ
POWER
INPUT
MODEL MC
HIGH MED LOW HIGH MED LOW MC
LR
WATTS
3000S/Sh 1.3 1.0 0.8 0.7 107 84 70 6.4 28.2 442
4000S/Sh 1.7 1.4 1.1 1.0 159 122 107 9.2 40.0 591
6000S 2.6 2.1 1.7 1.4 214 168 140 13.5 53.0 922
8000S 3.5 2.8 2.2 1.9 318 244 214 15.4 51.0 1028
NOTES:
SPLIT
SYSTEM
SYSTEM AMPS POWER INPUT WATTS
MODEL MC
LR
HIGH MED LOW
3000S/Sh 7.4 28.0 549 526 512
4000S/Sh 10.6 40.0 750 713 698
6000S 15.6 53.0 1136 1090 1062
8000S 18.2 51.0 1346 1272 1242
NOTES:
Option A: Dual Power / Valve Control
Option B: Sin
le Power / Electronic Control
1
A 15 amp dedicated circuit breaker
non GFI
is recommended for 3000S/Sh and 4000S/Sh s
stems.
2
A 25 amp dedicated circuit breaker
non GFI
is recommended for 6000S and 8000S s
stems.
1
Separate 115V / 60HZ power supplies are required for the Evaporator and the Condensin
Unit.
2
A 15 amp circuit breaker is recommended for all Evaporator models.
3) A 15 amp dedicated circuit breaker (non GFI) is recommended for 3000S/Sh and 4000S/Sh Con-
densin
Units
5
A 25 amp dedicated circuit breaker
non GFI
is recommended for the 8000S Condensin
Unit.
4
A 20 amp dedicated circuit breaker
non GFI
is recommended for the 6000S Condensin
Unit.
SINGLE 115V 60HZ POWER SUPPLY TO/FROM
EVAPORATOR