Do you have a question about the CENTRAL GB and is the answer not in the manual?
Describes the glass bulb capsule operating mechanism and its function.
Lists temperature ratings and corresponding bulb colors.
Details 'A' dimension measurement for flush types.
Details 'A' dimension measurement for recessed types.
Details 'A' dimension measurement for extended types.
Steps to determine K-factor length based on sprinkler type.
How to find the K-factor using the provided table.
Application of K-factor in branchline calculations.
Standard application requirements for GB/GB-QR sprinklers.
General requirements for installing GB/GB-QR sprinklers.
Step-by-step instructions for installing the sprinkler.
Guidelines for careful handling and proper storage.
Prohibits painting, coating, or altering sprinklers.
Owner's responsibility for operating condition and inspections.
Advises regular inspection by qualified services.
Procedures for replacing operated or damaged sprinklers.
Ensures nothing obstructs the sprinkler's discharge pattern.
Steps for removing system from service and replacing units.
Ensures systems are repaired and returned to service after activation.
Details the company's repair/replacement warranty.
Specifies information needed when placing an order.
Information on product availability and how to contact for service.
The Central GB & GB-QR Dry Pendent Sprinkler is an automatic sprinkler designed for specialized applications, particularly in environments prone to freezing or where sediment and foreign materials might accumulate in standard drop nipples. These sprinklers are available in both standard response (featuring a 5mm glass bulb) and quick response (with a 3mm glass bulb) versions.
The core of the sprinkler's operation lies in its glass bulb capsule, which contains a heat-sensitive liquid. Upon exposure to heat at its rated temperature, this liquid expands, causing the frangible capsule to rupture. This action releases the orifice seal, allowing water to discharge in a pre-designed spray pattern to control or extinguish a fire. The dry pendent design is specifically engineered to prevent water from accumulating in the drops leading to the sprinklers. This is achieved through a fitting that extends into the branch line, positioning the plug above the water line. This design ensures that even if residual water is present, the sprinkler can operate without the risk of freezing.