EasyManua.ls Logo

Centrometal CPREG-Touch - Page 38

Centrometal CPREG-Touch
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Opration mode
Technical instructions CONTROLLER - CPREG-Touch
38
5.6.3.1 - 5.6.4.2 1. CIRCUIT / 2. CIRCUIT
1.
2.
This schematic view is only possible to view, it is not possible to turn on / off / adjust individual elements.
General:
Specific elements can be individually adjusted and displayed for each heating circuit.
For example: Turn on / off the heating circuit, turn on / off the room corrector, select the type of heating circuit for each
circuit (radiator / floor), select the operation mode (daily / night).
Elements 1a - 8a have the same meaning as elements 1 to 8 (described above)
refer only to the 2nd heating circuit or or any heating mixing circuit involved
with respect to the number of circuits included.
8
8a
7
7a
6a
6
4
4a
5
5a
1
1a
9
3a
2a
2
3
It's possible to view all enabled mixing heating circuits (set temperatures, measured temperatures, heating type,
working of the pumps etc...). To enter this view press / button and then .
If there are more than 2 mixing heating circuits enabled you can switch view betwen them with buttons.
1 - Mixing valve (1.circuit)
2 - The calculated flow temperature (1.circuit)
3 - Current measured flow temperature (1.circuit)
4 - Heating type on 1. circuit (radiators or floor heating)
5 - Room corrector „CSK“ on 1. circuit (if turned off,
icon disappears)
6 - The desired temperature + deviation by room corrector
(1.circuit)
7 - Current measured room temperature (shown only
if the room corrector is turned on) in 1.circuit
8 - Mode (1.circuit) (day / night)
9 - Outer temperature (outer sensor)