Heat Detectors
Series 600
The Series 600 Heat Detector is attractive, durable and
features combination rate-of-rise and fixed temperature
operation. Heat detectors are available in 135°F and 200°F
temperature ratings.
Rate-of-rise detects heat by quickly responding to a rapid
temperature increase. Rate-of-rise units have a wide spacing
allowance of 50-foot centers. See specification table for
details.
Fixed temperature reacts to heat by responding to a specific
temperature setting.
Series 600 Detectors use the same reliable pneumatic rate-of-
rise element of former models, but offer added aesthetic
appeal.
The pneumatic rate-of-rise element responds to a rapid rise in
temperature, approximately 15°F. (8°C) per minute, by
expansion of air within the sealed chamber faster than it can
escape through a calibrated vent. The resultant increase in
pressure depresses the diaphragm, causing the electrical
contact to close the circuit.
The fixed temperature element uses a fusible alloy. When
activated, the external heat collector drops away to provide
quick visual confirmation that the element has operated.
The units protrude only 1-3/8 inch from the ceiling surface with
a junction box mounting. They have pleasing contours and an
all-white finish that conforms to ceiling aesthetics.
Installation
Each detector includes a patented reversible mounting plate.
In one position, it easily attaches to 3.25" or 4" octagonal box,
or plaster ring.
In reverse, the plate can be used for open wiring without a
junction box. A 1/4" space between detector and mounting
surface allows for wire connections. All mounting screws are
concealed.
The detector attaches easily to the mounting plate with a push
and twist motion. No tools are required.
Effective November, 2001
All rights reserved (11/01).
The Heat Detectors Series 600 are supplied
with the following standard features:
• Rate-of-Rise and Fixed Temperature
• One or Two-Circuit, Normally Open
• Easy Installation
• Low Profile
• Visual Indication
• Operation Testing
Description
Mounting plate is molded of white self-extinguishing thermo-
plastic rated at 221°F (105°C). The plate is extremely strong
yet adapts to uneven mounting surfaces.
Series 600 Testing Methods
Models 601/621 and 602/622 can be tested by the quick
application of heat from any convenient source. A portable hair
dryer is recommended. However, do not apply heat that
exceeds the fixed temperature rating of the detector.
Models 603/623 and 604/624 cannot be tested. However, the
fusible alloy element used is considered so reliable that testing
is not necessary.
3-1/4" or 4"
Octagonal Box
Question and Answer IconNeed help?

Do you have a question about the Chemetronics 601 and is the answer not in the manual?

Chemetronics 601 Specifications

General IconGeneral
BrandChemetronics
Model601
CategorySmoke Alarm
LanguageEnglish

Summary

Heat Detectors Series 600 Overview

Product Description

Details the attractive, durable, and dual-feature combination rate-of-rise and fixed temperature operation.

Installation Guide

Explains the patented reversible mounting plate and push-and-twist attachment for easy installation.

Testing Methods for Series 600

Describes testing procedures for models 601/621 and 602/622, noting models 603/623 and 604/624 are not tested.

Product Model Specifications

Model 601 and 621 Specifications

Details Rate-of-Rise and Fixed Temperature (135°F) detectors for normal temperature fluctuations.

Model 602 and 622 Specifications

Details Rate-of-Rise and Fixed Temperature (200°F) detectors for higher temperature fluctuations.

Model 603 and 623 Specifications

Details Fixed Temperature only (135°F) detectors for unusually violent temperature fluctuations.

Model 604 and 624 Specifications

Details Fixed Temperature only (200°F) detectors for high temperature fluctuations.

Technical and Safety Information

Screw Terminal Connections

Illustrates wiring for standard single circuit and dual circuit detectors.

Important Usage and Safety Notes

Emphasizes use for property protection, necessity of smoke detectors for life safety, and testing recommendations.

Electrical Ratings

Specifies voltage and amperage ratings for the detectors.

Listings and Approvals

Lists certifications and approvals from organizations like UL, FM, and CSFM.