Inverter heat pump solution
PAGE \*
MERGEFORMAT 18
Connect Wi-Fi on mobile phone and input password, and then control equipment by Wi-Fi. When
APP connects Wi-Fi successfully,“ lights on.
h. Running Status Checking
1. Press “ for 5 seconds, it will enter running status checking.
2. During this time, the display will show the status symbol “C0and its corresponding value.
3. Change status through and ”, the corresponding value also changes.
4. Press “ to quit “Running Status Checkingmode
5. Running status checking table:
Symbol
Content
Unit
C0
Inlet water temp
°C
C1
Outlet water temp
°C
C2
Ambient temp
°C
C3
Exhaust gas temp
°C
C4
Evaporator coil pipe temp
°C
C5
Return gas temp
°C
C6
Cooling coil pipe temp
°C
C9
Cooling plate temp
°C
C10
EEV opening angle
P
F. Testing
1. Inspect heat pump before use
a. The ventilating device and outlets are operating adequately and are not obstructed.
b. It’s prohibited to install refrigeration pipe or components in corrosive environment.
c. Inspect the electric wiring on basis of the electric wiring diagram and earthing connection.
d. Double confirm the main machine power switch should be off.
e. Inspect the air inlet and outlet.
2. Leakage detection notice and method
a. Leakage checking is prohibited in closed area.
b. The ignition source is prohibited during the leakage inspection. A halide torch (or any
other detector using a naked flame) shall not be used.
c. Leakage detection fluids can be applied with most refrigerants but the use of detergents