DTSU666 series and DSSU666 series
three phase electronic energy meter
ZTY0.464.1448
User manual
Page 10, Total 21
When the current is directly connected to the line, Ct shall
be set as 1.
0.1999.9
Voltage ratio, used for setting the voltage ratio of the input
loop;
When the voltage is connected to the line via the
transformer, Pt= the rated voltage of the primary loop / the
rated voltage of the secondary circuit;
When the voltage is directly connected to the line, Pt shall
be set as 1.0.
1645;
2n.2;
3n.1;
4E.1;
5O.1;
Communication protocol switches:
1Dl/T 645-2007
2None parity, 2 stop bits, n.2;
3None parity, 1 stop bit, n.1;
4Even parity, 1 stop bit, E.1;
5Odd parity, 1 stop bit, O.1;
01200
12400
24800
39600
4: 19200;
Communication baud rate:
0Communication baud rate to be 1200bps
1Communication baud rate to be 2400bps
2Communication baud rate is 4800bps
3Communication baud rate is 9600bps
4Communication baud rate is 19200bps
1247
Communication address
0n.34
1n.33
Option for wiring mode:
0n.34 represents three phase four wire;
1n.33 represents three phase three wire.
0:n01:E
The setting is 1, representing the allowed instrument energy
data clearance, which will be zero reset after clearing.
0:P1:Q
Pulse output: