EasyManua.ls Logo

ClearWater CD-2000 - Page 22

Default Icon
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Terminals 7 & 8: Booster Pump -240VAC,60Hz,8AMP,1HP.Useminimum#14AWG.120VAC,60Hz,16AMP,use
minimum #12 AWG. Wire from the terminal strip to the booster pump as indicated. The booster pump will be controlled by the
interlockbox.Inmanycasesthisfeatureisnotbeused;theoperationoftheremainingequipmentwillnotbeaffected.
Terminals 9 & 10: Ozone Generator -240VAC,60Hz,2AMPor120VAC,60Hz,4AMP.Hardwiretheelectricalcordon
theozonegeneratortotheterminalstripasindicated.Theozonegeneratorwillbecontrolledbytheelectricalinterlockbox.
Air Dryer: 120VAC,60Hz,1AMP.Plugtheairdryerintoastandardwalloutlet120VAC,60Hz.Theairdryershouldremain
energizedatalltimeswiththeexceptionoflongtermshutdownforservice.Theairdryercanbehardwiredtotheelectrical
interlockboxutilizingterminals1(120V)and3(neutral).
Using a bonding wire conforming with all local, state and national electrical codes (normally a #8 AWG), ground the
components to the grounding bar on the electrical interlock box and bond the electrical interlock box to a true earth
ground.
Electrical Connections - continued
120 VAC MODELS 240 VAC MODELS
1. Line in 120V 1. Line in 240V
2 Neutral in 2. Line in 240V
3. Neutral in 3. Neutral In
4. MCI in 4. MCI in
5. ORP Line in 5. ORP Line in
6. ORP Neutral 6. ORP Neutral
7. Booster Pump Out 120V 7. Booster Pump Line Out 240V
8. Booster Pump Neutral 8. Booster Pump Line OUt 240V
9. Ozone Generator Out 120V 9. Ozone Generator Out 240V
10. Ozone Generator Neutral 10. Ozone Generator Out 240V
Grounding Bar