Chapter 4 — Sequence of Operation
Part No. 750-184 4-3
diagram to determine the actual controls provided. The circuits and controls
normally used in the circuits follow and are referred to in the following
sequence of operation.
Limit Circuit:
Burner switch (BS)
Operating limit control (OLC) - pressure or temperature
High limit control (HLC) - pressure or temperature
Low-water cutoff (LWCO)
Gas-oil selector switch (GOS) - (Combination burner only)
Oil drawer switch (ODS)-Oil burner
Low oil temperature switch (LOTS) - (Nos. 4, 5 and 6 oil only)
Low gas pressures switch (LGPS)
High gas pressure switch (HGPS)
LE Proximity switch interlock
Fuel valve interlock circuit
Main gas valve auxiliary switch (MGVAS)
Oil valve auxiliary switch (OVAS)
Blower Motor Starter Circuit
Blower motor starter (BMS)
Air compressor motor starter (ACMS) (if provided)
Air purge valve (APV) (Nos. 5 or 6 oil only)
Running lnterlock Circuit
Blower motor starter interlock (BMSI)
Combustion air proving switch (CAPS)
Atomizing air proving switch (AAPS) (if provided)
Low Fire Proving Circuit
Low fire switch (LFS)
Pilot Ignition Circuit
Gas pilot valve (GPV)
Ignition transformer (IT)
Gas pilot vent valve (GPVV) (if provided)
Flame Detector Circuit
Flame detector (FD)
Main fuel valve circuit