Manual Comfort Control
Control Installation & Setup
PNE2002 Series Control
Page 11
Problem Solving
THIS TROUBLE SHOOTING GUIDE IS A REFERENCE ONLY.
FOR SERVICE OR WARRANTY REQUIREMENTS PLEASE REFER
TO THE END OF THESE INSTRUCTIONS
PROBLEM
PROBABLE CAUSE REMEDY
a Black – out a Wait
b Tripped Circuit Breaker b Reset
c Blown Fuse c Replace
Unit fails to
start
d Electrical Fault d Call Climate Technologies Service Provider
a Pump Seized a Isolate power and then take off top of pump
and try to free it. Some lubricant may help.
Pump fails
to start
b Pump Burnt Out b Call Climate Technologies Service Provider
a Float Valve Leaking a Check adjustment or replace sealWater
leaking
from
overflow
b Drain from Celdek Pads b Normal Operation
a Loose Delivery Tube a Check and tighten
b Break in tubing b Replace as necessary
Water
Droplets in
air stream
c Pump Delivers Excessive Water to
Pads
c Adjust the Dialflo to reduce the flow
a Inadequate Exhaust a Provide more open area to exhaust stale air
Excessive
humidity
b Outside humidity high b Turn pump off.
a Dirty Filters a Clean
b Dry Filters b Check water delivery system. Adjust if
necessary.
Inadequate
Cooling
c Dialflo not set correctly c Adjust Dialflo so that the pads have even
saturation.
a Unit located near odor source a Remove source
Unpleasant
Odor
b New Celdek filter smell b Smell will disappear after a period of
operation.
Rapid
formation of
white
deposits on
pads
High Mineral Content Bleed off should be set at maximum. More
regular maintenance may be required.