EasyManua.ls Logo

ClimateMaster ACDU03 - Pump Confi Guration; Valve Confi Guration

ClimateMaster ACDU03
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACDU03 Communicating Service Tool
Rev.: November 3, 2017
6
Geothermal Heat Pump Systems
VARIABLE SPD INTERNAL
PUMP CONFIGURATION
LOOP OPTION SINGLE
PUMP CONTROL FIXED
HEATING STAGE 1 60%
COOLING STAGE 2 75%
COOLING STAGE 1 50%
COOLING STAGE 2 70%
PREVIOUS SELECT
3.4 PUMP CONFIGURATION
vFlow™ vs internal ow control pump can be controlled either
through temperature differential (Delta T) or can be set to
speci c speed ( xed; % of full speed for each heat and cool
stage).
Can be con gured for either single pumping or parallel
pumping.
Con gure temperature differentials at the thermostat for
vFlow™ units with an internal ow control pump.
Adjust the Pump Con guration settings using the up/down
arrow buttons. Press the center button to select each item.
Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
Maximum Heat LWT (valid range based on speci c model;
refer to model IOM). Minimum Cool LWT (valid range based
on speci c model; refer to model IOM).
NOTE: Refer to section 3.6.3 for multi-unit con guration
instructions.
To control vs pump by xed speed, select ‘Pump Control’,
press , use down arrow to select ‘Fixed’, and press to
save.
Default stored in control. Valid range: 15% - 90% (in 1%
increments)
Heating Stage 1 Cooling Stage 1
Heating Stage 2 Cooling Stage 2
If Pump Con guration is set to ‘VS PUMP PARALLEL’, valid
range changes to 50-90% (in 1% increments).
3.5 VALVE CONFIGURATION
Con gure temperature differentials at the thermostat for
vFlow™ units with a motorized modulating valve.
Adjust the Valve Con guration settings using the up/down
arrow buttons. Press the center button to select each item.
Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
NOTE 1: Minimum and Maximum degree values are shown
only when the control is con gured with the appropriate
values.
NOTE 2: Refer to section 3.6.3 for multi-unit con guration
instructions.
3.5.1 MODULATING VALVE OFF POSITION
For certain commercial multi-unit applications, the modulating
valve can be kept slightly open by choosing values 3.3-4.0.
MODULATING VALVE
CONFIGURATION
OFF POSITION 0.0
VALVE CONTROL DELTA T
HEATING DELTA T 7 F
COOLING DELTA T 10 F
MAXIMUM HEAT LWT 80 F
MINIMUM COOL LWT 40 F
PREVIOUS SELECT
VARIABLE SPD INTERNAL
PUMP CONFIGURATION
LOOP OPTION PARALLEL
PUMP CONTROL DELTA T
HEATING DELTA T 7 F
COOLING DELTA T 10 F
MAXIMUM HEAT LWT 80 F
MINIMUM COOL LWT 40 F
PREVIOUS SELECT