EasyManua.ls Logo

CLIVET CONTROL4 NRG - Page 102

CLIVET CONTROL4 NRG
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
102
M0CZ00007-03
SYSTEM COMPONENT CONFIGURATION
select 3
select 4
select
2
press for 2 sec.
1
3
4
Electricity meter
Address allocation:
170 Energy meter 1 (absorbed)
171 Energy meter 2 (absorbed)
172 Energy meter 3 (Production)
The meter is preconfigured with address 170
Meter address setting:
1. Power up and connect the meter to the CONTROL4 NRG serial
line
2. Go to the Other parameterspage of CONTROL4 NRG (See
screenshots opposite)
3. Set Device address field = 170
4. Set Parameter address field = 2
5. Set Enter value field = New Modbus ID (171 or 172)
6. Press the "Write" button
7. Set Parameter address field:
Single-phase model = 251
Three-phase model = 243
8. Set Enter value field = 49600
9. Press the "Write" button
10. Switch the meter off and on again and check for correct addressing
Verification of address change:
1. From the Other parametersscreen of CONTROL4 NRG:
2. Set Device address field with the new Modbus address (171 or 172
depending on what has been set)
3. Set Parameter address field = 2
4. Press the Readbutton and check that the device responds.
NOTE:
if it is necessary to address more than one meter, only connect one
meter at a time to the serial line to carry out the addressing procedure.
2
2
1
Vedere pag. 110 Accesso parametri/visualizzazione