13
M0CZ00007-03
HEAT PUMP
3 - Compensated supply water set point:
set the compensation curve that corrects the water set point value,
depending on the outdoor air temperature value.
CHANGE OF SET POINT, FROM FIXED TO
COMPENSATED
1 - Select the single circuit to customise the set point
2 - Select "fix"
select 2
select 3
Example
Outdoor air >= 30°C
supply water set point = 7°C
Outdoor air <= 15°C supply water set point = 12°C
MODIFICATION OF SUPPLY SET POINT
4 - Select supply set
5 - Set the required values:
Max 12°C
Min. 7°C
select 4
1
2
3
5
4