HEAT PUMP
MODIFY THE OUTDOOR TEMPERATURE:
5 - select
6 - Set the required values:
Max 30°C
Min. 15°C
7 - Modify the correction
8 - Modify the correction
example: + 1.2°C
The correction can be used to modify the climatic curve rapidly.
Example:
Outdoor air = 30°C supply water set point = 7°C
Outdoor air = 15°C supply water set point = 12°C
Correction + 1.2°C in Summer
Values after the correction:
Outdoor air = 30°C supply water set point = 7+1.2 = 8.2°C
Outdoor air = 15°C supply water set point = 12+1.2 = 13.2°C
For the winter correction, follow the same procedure.
select 5
select 7
6
8
5
7