SYSTEM COMPONENT ADDRESSING
ZONE MODULE (HEATED TOWEL )
The module operation opens and closes the valve, according to the
temperature detected by the thermostat, in the cooling mode, the
module closes the valve.
The module can be used also to control 1 radiant circuit.
The area module must be powered at 230 Vac 50 Hz.
Assembly on DIN guide
Type of cable used:
2x0.35 mm
2
with screen on gnd
Maximum distance: 15 m
Termination
No
YES
Addressing can be done using the selectors on the RS485 module.
Follow this procedure:
1 - Disconnect power supply to the RS485 module and mixing module
2 - Set the address with the selectors on the RS485 module
S5 = hundreds. Must always be set to OFF
S3 = tens
S4 = unit
example: 17= S3 =1 , S4 =7
3 - Set parameters 34 and 35 under Other parameters in the Advanced settings of CONTROL4 NRG (see page 110)
For module RS485, see page 88
Parameters to be modified
Parameter
Mnemonic
Name
Description Value
33 Index Device address 17,18...
34 Baud Rate
Baud Rate 0=4800 1 :9600
2 :19200
1
35 Parity
Parity 0=NO / 1=Odd 2=Even
supervision serial
0
TERMINATION
JUMPER