SYSTEM COMPONENT ADDRESSING
MIXING MODULE
Parameters to be modified
Parameter
Mnemonic
Name
Description Value
33 Index Device address 50..,52
34 Baud Rate
Baud Rate 0=4800 1 :9600
2 :19200
1
35 Parity
Parity 0=NO / 1=Odd 2=Even
supervision serial
0
RS485 MODULE BT2 EXSTERNAL TEMPERATURE READING PROBE
PE3S0006 - Option
Enable BT2 probe:
System setting menu (page 110)
Parameter menu
Setting parameter 1 = mixing module
3
J
3S
4S
ON
ON
S1
S 2
ON
RS485
LR
LV
J 1
G
N
D
-
+
5S
Mixing unit control module for managing a section of the circuit at a
different temperature to that of the main system.
The area module must be powered at 230 Vac 50 Hz.
Mounting on a DIN rail
Type of cable used:
2x0.35 mm2 with screen on GND
H
6
0
105
90
P
L
AP1
AP2
H
6
0
36
90
P
L
TERMINATION
JUMPER
Termination
No
Yes
Addressing can be done using the selectors on the
RS485 module.
Follow this procedure:
1 - Disconnect power supply to the RS485 module and
mixing module
2 - Set the address with the selectors on the RS485
module
S5 = hundreds. Must always be set to OFF
S3 = tens
S4 = unit
3 - Set parameters 34 and 35 under Other parameters
in the Advanced settings of CONTROL4 NRG (see
page 110)
TERMINATION
JUMPER