M2E240P5-03 12/09/07 page 10
Contact with parts that could become live when the unit is
started up can result in electric shock, burns or death by
electrocution.
When there is no need for circuits to be powered up, set the
isolating switch on the power line to the OFF position,
padlock it and post a warning sign.
MOVING PARTS
Contact with the fan rotors can cause injury.
Before removing the protective grilles or the fans
themselves, make certain the isolating switch on the power
line to the unit is set to the OFF position and padlocked,
and post a warning sign.
Before removing the protective grilles or the fans
themselves, make certain the isolating switch on the power
line to the unit is set to the OFF position and padlocked,
and post a warning sign.
REFRIGERANT
In the event of safety valves coming into operation and
releasing refrigerant gas, persons in the vicinity can be
injured or suffer toxic effects. Always wear suitable clothing
and protective goggles when working in potential hazard
areas.
In the event of refrigerant gas escaping, refer to the “Safety
datasheet” for the particular refrigerant.
If an open flame or heat source is brought into contact with
the refrigerant, or the pressurized gas circuit should
overheat (e.g. during welding operations), this can cause
explosion or fire. Do not position any heat source within the
hazard area.
Maintenance or repair operations involving welding must be
carried out with the system emptied of refrigerant.
WATER SYSTEM
Defects affecting pipelines, connections or valves and other
control componentry can result in water being leaked or
sprayed from the system, occasioning damage to property
or causing short circuits in the unit.
Make certain all hydraulic connections are securely made,
following the directions given in the present manual.
REFRIGERANT SAFETY CHARGE
R-407C
01
Identifying elements
for the substance
Product name: forane 407C
N°SDS 01965/1
Supplier: ELF ATOCHEM ITALIA
Via G.Murat 17, 20159 Milano tel. 02/668111
02
Information
concerning
composition of
components
Chemical nature of the compound
Mixture based on:
Forane 32(difluoromethane) (N° CAS: 75-10-5)
Forane 125 (pentafluoroethane) (N° CAS: 354-33-6)
Forane 134a (1.1.1.2 tetrafluoroethane) (N° CAS: 811-97-2)
03
Identification of risk
Greatest physical and chemical dangers:
Thermal decomposition in toxic and corrosive products
04
First-aid measures
General information:
Inhalation: Carry the victim into the open air. Resort to oxygen or artificial respiration if necessary.
Contact with skin: Frostbite must be treated in the same way as burns.
Contact with the eyes: Immediate rinsing in abundant water. If irritation should continue, consult an ophthalmologist.
Medical instructions: Do not administer catecholamines
(due to the cardiac sensitisation caused by the product)
05
Fire prevention
measures
Specific dangers: Thermal decomposition into toxic and corrosive products. Hydrofluoric acid. Carbon monoxides.
Specific means of intervention: Cool containers/cisterns with jets of water. Prevent any sparks or flames.
Do NOT smoke.
Special protection systems for fire-fighting squads: Carry breathing apparatus and wear protective clothing.
06
Measures to take in
case of accidental
spillage
Individual precautions: Avoid contact with the skin, eyes and inhalation of vapours. Use personal protection devices.
In an enclosed space: ventilate or use breathing apparatus (risk of suffocation). NO SMOKING ALLOWED
Precautions for environmental protection: Minimise the amount of waste deposited in the environment.
07
Manipulation and
storage
Technical measures/precautions.
Form of storage and manipulation applicable to the products: PRESSURIZED GAS.
Ensure adequate ventilation and evacuation for the level of equipment.
Advice for use: Prevent sparks and contact with hot surfaces. DO NOT SMOKE.
Technical measures/Storage procedures: Store at ambient temperature in the original container. Keep away from
flames, hot surfaces and sparks. Store in a cool, well-ventilated place. Protect full containers from sources of heat to avoid
excessive pressures.
Recommended: Ordinary steel.
Avoid: Alloy containing more than 2% magnesium.
Plastics.
08
Control of individual
exposure/protection
Precautionary measures to be taken: Ensure a sufficient exchange of air and/or suction in workplaces.
Control parameters.
Exposure limits: There is no F-USA limit value
Forane 134a Elf recommended limit value: VME=1000ppm
Forane 32 Elf recommended limit value: VME=1000ppm Forane 125 Elf recommended limit value: VME=1000ppm
Respiratory protection: In case of insufficient ventilation, carry suitable breathing apparatus.
Protection for the hands: Gloves
Protection for the eyes: Protective eyewear.

Questions and Answers: