M02S40N16-00 WSA-XEE 122-402 33
code detailed description t.i. module input t.a.
ee126: Faulty probe - source 2 temperature AI 985 circuit 1 T2 X1 A
ee127: Faulty probe - Suction temperature AI 94U driver T2 X2 A
ee128: Faulty probe - discharge pressure AI 985 circuit 1 T2 X3 A
ee129: Faulty probe - suction pressure AI 94U driver T1 X1 A
ee130: Faulty probe - Recovery gas temperature AI 965 recovery T1 X1 A
ee131: Faulty probe - Recovery pressure AI 965 recovery T2 X7 A
ee132: Faulty probe - Water recovery inlet AI 965 recovery T1 X2 A
ee133: Faulty probe - Water recovery outlet AI 965 recovery T1 X3 A
ee135: Bios wrong version 985 circuit 1 A
105: Low overheating Thermostatic C1 A
fF109: Low pressure from analogic input DI 985 circuit 1 T3 X7 A/M
110: Pre-alarm - low pressure COOL mode A
111: Pre-alarm - low pressure HEAT mode A
fF112: Low pressure from analogic input AI 94U driver T1 X1 A/M
fF113: High pressure from digital input DI 985 circuit 1 T3 X8 A/M
114: Pre-alarm - high pressure A
fF115: High pressure from analogic input AI 985 circuit 1 T2 X3 A/M
116: Pre-alarm max. compression ratio (high pressure / low pressure) A
fF117: Min. compression ratio (high pressure / low pressure) A/M
FF119: Alarm max. compression ratio (high pressure / low pressure) M
FF134 Empty circuit AI 94U driver T1 X1 M
136: Defrost: low gas temperature Logico 985 X2 M
fF137: Oil pressure DI 985 DL1 A/M
138: Low condensing pressure Logico 985 X3 A
fF139: Maximum saturated condensation temperature Logico A/M
fF140: Minimum saturated condensation temperature Logico
A/M
fF141: Maximum saturated evaporation temperatur Logico A/M
fF142: Minimum saturated evaporation temperatur Logico A/M
fF143: Maximum compression ratio Logico A/M
FF144: Minimum compression ratio Logico M
fF145: Maximum engine torque Logico A/M
iI002: Low water pressure DI 687 central T5 DU1 A/M
iI006: Flow switch utility side DI 687 central T3 X8 A/M
II007: Freeze alarm utility side M
ii008: Utility side pumps On for antifreeze alarm A
II009:
COOL:
outlet temperature higher than inlet temperature
HEAT:
inlet temperature higher than outlet temperature
A
iI120: Flow switch source side DI 985 circuit 1 T2 X4 A/M
II121: Freeze alarm source side A
II042: FCI module, system pressure DI 955 FCI X3 M
II043: FCI module, antifreeze alarm Logico 955 FCI X1 M
ii047: FCI module, water ow alarm DI 955 FCI X4 A
ii052: Recosery module, ow alarm DI 965 REC X6 A
ii053: Recovery module, system pressure DI 965 REC X6 A