Admissible water flow rates
SIZE 81 91 101 121 141
Minimum flow-rate Qmin [l/s] 0,48 0,54 0,66 0,78 0,90
Maximum flow-rate Qmin [l/s] 0,92 1,03 1,26 1,49 1,72
Fouling Correction Factors
Internal exchanger
m²C/W F1 FK1
0,44x10 (-4) 1 1
0,88x10 (-4) 0,96 0,99
1,76x10 (-4) 0,93 0,98
The cooling performance values provided in the tables are based on the external exchanger having clean plates (fouling factor 1). For dierent fouling factor values, multiply the
performance by the coecients shown in the table.
F1 = Cooling capacity correction factors
FK1 = Compressor power input correction factor
General technical data