Admissible water flow rates
SIZE 81 91 101 121 141
Minimum flow-rate Qmin [l/s] 0,48 0,54 0,66 0,78 0,90
Maximum flow-rate Qmin [l/s] 0,92 1,03 1,26 1,49 1,72
Fouling Correction Factors
Internal exchanger
m²C/W F1 FK1
0,44x10 (-4) 1 1
0,88x10 (-4) 0,96 0,99
1,76x10 (-4) 0,93 0,98
The cooling performance values provided in the tables are based on the external exchanger having clean plates (fouling factor 1). For dierent fouling factor values, multiply the
performance by the coecients shown in the table.
F1 = Cooling capacity correction factors
FK1 = Compressor power input correction factor