18
5 - ELECTRICAL CONNECTIONS
AP10 Gateway Modbus RS485
AP12 Remote interface terminal
AP13 Remote interface
AP14 Gateway LonWorks
APBK
Gateway Bacnet
XC Terminal block of Customer connections
5.8 COMUNICATION
Cable "A" requirements:
Couple of conductors twisted and shielded
Section of conductor 0.22mm2…0,35mm2
Nominal capacity between conductors < 50 pF/m
nominal impedance 120 Ω
Recommended cable BELDEN 3105A
A
A
A
A
A