12 WSN-XIN 21-141 M0V940M13-06
4.3 Direction of air supply
The unit is delivered with the air supply upward.
The air supply may be directed depending on the installation location.
To adjust the direction:
•
Unscrew the xing bolts on the fan cap.(4 for size 21-71, 10 for size 81-141).
•
Remove the cap and rotate.
•
Fix the cap using the bolts previously removed.
4.4 Condensate water
When a heat pump is running it produces a considerable amount of water due to the defrosting cycles of the external coil.
The condensation must be eliminated in a manner to avoid wetting pedestrian areas.
With extensive very cold outdoor temperatures, condensation could freeze outside the unit blocking the ow and causing a slow build-up of
ice; therefore special attention must be paid to eliminating condensation, raising the unit o the ground and evaluating whether antifreeze
elements should be installed.
A. Condensate discharge connection