37 | Modbus Installation
Modbus Parameters
The MHTC uses the following parameters for communication:
*Default, may vary for multi-unit orders.
It is important to note that the signaling type, transmission mode, baud rate, data bits and stop
bits cannot be modified. Parity and unit address can be modified as required.
The following points may be mapped for control:
Table 7: MHTC Humidifier Modbus Parameters
Reads/writes a
control signal to
the humidifier
Writes a control signal to
the humidifier. This input
only works if humidifier is
set to network control
NetSensor set to 1) in
the control settings. If
the system is set to
network control no signal
is detected, the unit will
display the modbus
timeout error.
Reads/Writes
the desired
space setpoint
Used when Hum_Control
= 2 or 3 only
Remotely
disables
humidifier
0 = Allow normal
humidifier operation
1 = Remotely disables
the humidifier
Selects the
control type
that the
humidifier
operates on
0 = Demand Signal
1 = On/Off Signal
2 = RH Sensor Value
(Use Proportional control
method)
3 = RH Sensor Value
(Use Proportional-Integral
control method)
Switches
between hard
wired or
network control
signal
0 = Wired Analog
Sensor/Demand
1 = Modbus/Remote
Sensor/Demand
Indicates
output from
humidifier
stage 1