Modbus Installation | 38
Variable
Name
Description
Addr
Type
Format
Range
Unit
R/W
Details
Stage2Dem
Indicates
output from
humidifier
stage 2
30026
Input
Register
Integer
0 or 1
-
Read
0 = Inactive
1 = Active
Stage3Dem
Indicates
output from
humidifier
stage 3
30027
Input
Register
Integer
0 or 1
-
Read
0 = Inactive
1 = Active
Warning
Indicates
warning status
30015
Input
Register
Integer
0 or 1
-
Read
0 = No warning
1 = Warning
Service
Indicates
maintenance
requirement
30016
Input
Register
Integer
0 or 1
-
Read
0 = No service required
1 = Service required
Fault
Indicates fault
status
30017
Input
Register
Integer
0 or 1
-
Read
0 = No error
1 = Error(s) detected
Cleaning
Indicates
automatic
stage cleaning
cycle status
30018
Input
Register
Integer
0 or 1
-
Read
0 = Inactive
1 = Active
TankDrain
Indicates
automatic tank
drain status
30019
Input
Register
Integer
0 or 1
-
Read
0 = Inactive
1 = Active
PumpRunHr
Displays pump
operational
hours
30100
Input
Register
Integer
0 -
65535
10
min
Read
1Bit = 10min (max.
10’922h)
UVRunHr
Displays UV
lamp
operational
hours
30101
Input
Register
Integer
0 -
65535
10
min
Read
1Bit = 10min (max.
10’922h)
ServTime
Displays unit
operational
hours
30102
Input
Register
Integer
0 -
65535
10
min
Read
1Bit = 10min (max.
10’922h)
Security
Indicates
security loop
status
(humidifier
terminals 1 and
2)
30200
Input
Register
Integer
0 or 1
-
Read
Humidifier will only
operate when security
loop is closed.
0 = Off
1 = On
TankLevel
Max Level
Sensor
30202
Input
Register
Integer
0 or 1
-
Read
0 = Tank below full level
1 = Tank full
System
Ready
Indicates when
the humidifier
is ready to
commence
stages
30013
Input
Register
Integer
0 or 1
-
Read
0 = System busy
(cleaning or draining)
1 = System ready to
Humidify