Modbus Installation | 42
Configures
how
humidifier
responds to
modbus
controls
0 = Disable operation of
humidifier (Default Value)
255 = Allow operation of
humidifier within limits
specified by CapLimit
Notes:
- If a valid Modbus message is
not received within the timeout
windows, this parameter reverts
to 0.
- This value cannot be set when
the FORCE DRAIN is activated
as. FORCE DRAIN temporarily
sets this to value 0.
- Jumper J26 must be installed
to write any parameter over the
Modbus. J26 sets it into the
control mode.
- Opening of the hardwired
security loop (terminals 1 and 2)
will override operation even if
255 is written.
Imposes a
maximum
output limit
as
percentage
of unit
capacity.
Values outside of 25 - 100%
return an error.
Default on startup = 25.
Manually
initiates a
drain period.
0 = Normal operation
(Default)
255 = Initiate a 20 minute
timer during which the drain
is active.
Notes:
- During a force drain,
humidification ceases.
- Writing 0 during 20 minute
period will cancel the drain.
- After 20 minutes this value will
revert to 0 and the humidifier
will resume normal operation.
Writes a new
Modbus
address for
the
humidifier.
Default = 1. Values of 1 -
255 are acceptable.
Changes to this variable do
not take effect until the
humidifier has been power
cycled.
Sets the
Modbus
baud rate
Changes to this variable do
not take effect until the
humidifier has been power
cycled.
0 = 4800 bps
1 = 9600 bps (Default)
2 = 19200 bps
Changes to this variable do
not take effect until the
humidifier has been power
cycled.
0 = No parity
1 = Even parity (Default)
2 = Odd parity