43 | Modbus Installation
Allows the
run hour
counter to be
reset to 0,
typically used
following
maintenance.
Requires that HumEnable is
set to 0 (disabled) first or
ILLEGAL DATA error will
occur.
255 = Reset the run time
hours (reported in RunHrs)
to 0.
Value reverts to 0 after
operation is complete.
Switches
between
imperial
(lbs/hr) and
metric
(kg/hr) units.
0 = Imperial (lbs/hr)
1 = Metric (kg/hr)
Changes values reported in
Model (40205) and
SteamOutput (30105).
Allows writing
of humidifier
capacity to
match model.
Value represents maximum
unit capacity, in lbs/hr, at
100% Fill Off Amps.
Value cannot be written
while HumEnable = 255
(operational).
The MES-005 would be
written as 5. (Default = 8)
Reads the jumper (J1 thru 6)
pin settings and reports the
voltage:
0: 110-120V (J6 installed)
1: 208V (J6 installed)
2: 220-240V (J5 installed)
3: 230V
4: 277V (J4 installed)
5: 347V
6: 380V (J3 installed)
7: 400V (J3 installed)
8: 415V (J3 installed)
9: 440-480V (J2 installed,
Default)
10: 550-600V (J1 installed)
0 = Single phase
1 = 3 phase (Default)
2 = 3 phase (6 electrode)
Resets the
controller
and restarts
in standby.
Write 255 to this register to
reset the control. The
controller will reset, restart,
and remain in standby
mode. After completion:
- WasReset (40002 )will read
255 (reset has occurred)
- HumEnable (40003) will
read 0 (unit is disabled)
Sets the
permissible
window for
modbus data
to be written.
Each integer is a multiple of
200mS. Maximum time of
51 secs occurs when the
register reads 255.
A value of 0 disables the
timeout, but can only be
written with HumEnable
(40003) is set to 0
(disabled).