Modbus Installation | 44
Displays
current draw
in Amps.
Each bit represents 0.0024
Amps, therefore 1 Amp =
416 bits.
The Amp value does not
clear when security loop is
open and the demand is 0.
The last detected value
remains in the register.
Displays the
steam output
in either
Metric of
Imperial
units.
Units are defined in Units
(register 40204). Unit
includes decimal point as
integer value. Example:
17 = 1.7 (kg/hr or lbs/hr)
This variable does not clear
when the security loop is
open and the demand 0. The
last detected value remains
in the register.
Steam production hours
since last reset. Max
possible 2000 hrs of
operation. Each integer is a
multiple of 5 minutes.
Example:
1 = 5minutes
12 = 60 minutes (1 hr)
Displays unit
firmware
version.
Example: 352 = Version
3.52
Displays
status of
various
components.
Significant bits: 1 (Bit 0), 2
(Bit 1), 4 (Bit 2), 8 (Bit 3), 16
(Bit 4), 32 (Bit 5), 64 (Bit 6),
128 (Bit 7).
Bit 0 = Contactor
Bit 1 = Fill Valve
Bit 2 = Drain Valve
Bit 3 = Blower pack fan
Bit 4 = Collective fault (see
30108 for details)
Bit 5 = Humidifier Active
A “1” in the appropriate bit
location indicates that the
component is active.
Displays the
maximum
capacity of
humidifier.
The maximum amount of
steam per hour that the
humidifier can produce in
lbs/hr. This value is copied
from Model (40205).
Displays the
value of
modulating
signal when a
local
modulating
humidistat is
used.
Values are displayed as
whole numbers with 2
decimals places. Example:
1023 = 10.23 volts
500 = 5.00 volts
A constant value of 1023
can indicate the jumper J10
is installed.
Indicates the
presence of a
fault and
which fault
has been
detected.
0 = (Amber LED 1 flash)
Excess current.
1 = (Amber LED 3 flash) High
water level, no current.
2 = (Amber LED 2 flash) No
current detected
3 = (Amber LED 4 flash) End
of cylinder life.