Modbus Installation | 44
Current
Displays
current draw
in Amps.
30104
Input
Register
Integer
0 -
12495
Amps
Read
Each bit represents 0.0024
Amps, therefore 1 Amp =
416 bits.
The Amp value does not
clear when security loop is
open and the demand is 0.
The last detected value
remains in the register.
SteamOutput
Displays the
steam output
in either
Metric of
Imperial
units.
30105
Input
Register
Integer
0 - 300
lbs/hr
kg/hr
Read
Units are defined in Units
(register 40204). Unit
includes decimal point as
integer value. Example:
17 = 1.7 (kg/hr or lbs/hr)
This variable does not clear
when the security loop is
open and the demand 0. The
last detected value remains
in the register.
RunHrs
Run hour
Counter
30106
Input
Register
Integer
0 -
24000
min
Read
Steam production hours
since last reset. Max
possible 2000 hrs of
operation. Each integer is a
multiple of 5 minutes.
Example:
1 = 5minutes
12 = 60 minutes (1 hr)
Firmware
Displays unit
firmware
version.
30113
Input
Register
Integer
-
-
Read
Example: 352 = Version
3.52
Status
Displays
status of
various
components.
30107
Input
Register
Integer
0 - 128
-
Read
Significant bits: 1 (Bit 0), 2
(Bit 1), 4 (Bit 2), 8 (Bit 3), 16
(Bit 4), 32 (Bit 5), 64 (Bit 6),
128 (Bit 7).
Bit 0 = Contactor
Bit 1 = Fill Valve
Bit 2 = Drain Valve
Bit 3 = Blower pack fan
Bit 4 = Collective fault (see
30108 for details)
Bit 5 = Humidifier Active
A “1” in the appropriate bit
location indicates that the
component is active.
MaxOutput
Displays the
maximum
capacity of
humidifier.
30111
Input
Register
Integer
0 - 30
lbs/hr
Read
The maximum amount of
steam per hour that the
humidifier can produce in
lbs/hr. This value is copied
from Model (40205).
Modulation
Displays the
value of
modulating
signal when a
local
modulating
humidistat is
used.
30102
Input
Register
Integer
0-1023
-
Read
Values are displayed as
whole numbers with 2
decimals places. Example:
1023 = 10.23 volts
500 = 5.00 volts
A constant value of 1023
can indicate the jumper J10
is installed.
FaultCode
Indicates the
presence of a
fault and
which fault
has been
detected.
30108
Input
Register
Integer
0-
32768
-
Read
0 = (Amber LED 1 flash)
Excess current.
1 = (Amber LED 3 flash) High
water level, no current.
2 = (Amber LED 2 flash) No
current detected
3 = (Amber LED 4 flash) End
of cylinder life.