Uninterruptible power supply
COVER MR
600 kVA
User manual

Table of Contents

Questions and Answers

  • C
    Christine RiversAug 15, 2025
    What to do if my Cover MR UPS has mains but no output when power is off?
    • K
      Kathleen CollierAug 15, 2025
      When the Cover UPS has mains power but no output when the mains are off, begin by inspecting the battery for faults or damage. Also, check the charger and wiring connections to ensure they are secure. The issue could stem from a faulty battery, a charger problem, loose wiring, an open battery breaker, or the UPS remaining in bypass output status after a significant overload.
  • M
    mkingAug 18, 2025
    Why is my Cover MR UPS in bypass status after startup?
    • L
      Lindsay BrooksAug 18, 2025
      If your Cover UPS outputs 220V AC power but operates in bypass mode, it could be due to the load exceeding the UPS's rated output capacity. Try reducing the load. If the bypass is temporary and caused by the load startup, it should return to normal automatically.
  • J
    Joshua HansonAug 21, 2025
    Why does my Cover MR shut down automatically after some time?
    • R
      Ronald HoltAug 21, 2025
      If your Cover UPS shuts down automatically some time after startup, especially when running on battery, it's likely due to the battery running out of power and the system protecting itself from undervoltage. Once the mains power returns, the system will automatically start charging the battery. To further protect the battery, disconnect the battery breaker after an undervoltage protection event.
  • D
    Dalton MartinezAug 25, 2025
    What to do if Cover MR UPS stops outputting immediately after turning on the load?
    • J
      John RamosAug 26, 2025
      If your Cover UPS stops outputting immediately after turning on the load, it could be due to a serious overload or a short circuit in the output circuit. Reduce the load to a proper capacity or find the source of the short circuit. When restarting the UPS, ensure you start the load devices in the correct sequence, beginning with the largest power device and moving to the smallest.
  • R
    Richard WuAug 28, 2025
    Why Cover MR UPS buzzer beeps long and shows battery low-voltage?
    • V
      victor85Aug 28, 2025
      If the Cover UPS buzzer beeps for a long time and the touch screen shows a low battery, it means the grid voltage is too low, causing the UPS to operate in battery inverting mode and eventually deplete the battery. Check the grid voltage and restore it to its normal range.
  • C
    Crystal BowenSep 1, 2025
    What to do if Cover MR UPS fuse keeps blowing after installation?
    • J
      Jacqueline BarreraSep 1, 2025
      If the Cover UPS fuse blows or trips off after installation when closing the breaker or power supply switch, it suggests that the three-phase input wire is incorrectly connected. Double-check the wiring connections to ensure they are properly configured.
  • A
    Alexis SimsSep 4, 2025
    Why does Cover MR beep intermittently when mains are present?
    • S
      seansmithSep 4, 2025
      If the Cover UPS buzzer beeps intermittently when there is mains power, it indicates that the mains voltage or frequency is outside the allowable range for the UPS. Check the mains voltage and frequency to ensure they are within the specified limits.
  • L
    Lisa WilsonSep 7, 2025
    What causes Cover UPS to work but load system to halt during outage?
    • J
      Justin SmithSep 7, 2025
      If the Cover UPS works normally with mains power, but the load system halts during a power outage while the UPS continues to operate, it suggests a grounding issue. Improve the grounding to reduce the float voltage between the neutral wire and the grounding wire.
  • T
    Taylor HammondSep 12, 2025
    What does it mean if FAULT indicator is on Cover MR UPS power unit?
    • T
      Tracy HuberSep 12, 2025
      If the FAULT indicator of a power unit on your Cover UPS is lit, it indicates that the power module is faulty and needs to be replaced promptly.

Summary

Safety and Environment

Safety Announcements and Instructions

Essential safety guidelines for operating and maintaining the UPS.

Operation, Maintenance, and Environmental Requirements

Procedures for safe operation, maintenance, and environmental conditions for the UPS.

UPS Overview and Functionality

Product Introduction and Features

Overview of the MR series UPS, its capabilities, and design.

Work Principles and Modes

Detailed explanation of UPS operation, including diagrams and work modes.

Structure, Panel, and Alarms

UPS components, operation panel layout, and alarm functions.

Module Information

Details on power modules, bypass modules, and control boxes.

Installation and Wiring

Installation Procedures and Preparation

Steps for UPS installation, including tools, environment, and mechanical setup.

System Wiring and Parallel Connections

Instructions for electrical wiring and connecting multiple UPS units.

System Checks and Testing

Procedures for verifying electrical connections and performing UPS tests.

Operation and Settings Management

Touch Screen Interface Navigation

Guide to the UPS touch screen menu, main page, and status display.

Parameter Configuration

Settings for system, battery, modes, functions, communication, and debug.

UPS Startup, Shutdown, and Mode Switching

Procedures for operating the UPS, including start/stop and bypass modes.

Emergency Power Off (EPO)

Instructions for using the Emergency Power Off function.

Maintenance and Troubleshooting

Maintenance Guide and Battery Care

Preventive maintenance, safety, battery charging, and replacement guidelines.

Troubleshooting Common UPS Faults

Diagnosing and resolving abnormal phenomena and system faults.

Logistics and Storage

Package, Transportation, and Storage

Guidelines for handling, transporting, and storing the UPS unit.

Cover MR Series Specifications

General IconGeneral
CategoryUPS
Input Frequency50/60Hz
Output Frequency50/60Hz
Battery TypeSealed Lead Acid
Protection FeaturesOverload, short circuit, surge protection
Communication InterfaceUSB
Operating Temperature0-40°C
Storage Temperature-15°C to 45°C
Humidity5% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model