14 COZY TOP VENT GRAVITY GAS WALL HEATER
VENT INSTALLED
FRONT PANEL INSTALLED
VENT
HOLD DOWN
PLATE
HEADER
FURNACE
SIDE RAIL
BASE PLATE
PANEL
FIGURE 8 – TYPICAL VENT INSTALLATION
VENT CAP MUST BE MINIMUM 2 FEET
HIGHER THAN ANY POINT WITHIN
10 FEET OF THE VENT CAP
10 FEET
LISTED
VENT CAP
STORM
COLLAR
ROOF
FLASHING
HEIGHT FROM HEADER PLATE
TO THE VENT CAP TOP MUST
BE 6 FEET MINIMUM
1 INCH MIN. CLEARANCE TO COMBUSTIBLES
LISTED 4" ROUND B VENT
OVAL TO ROUND
ADAPTER
OVAL B/W VENT
(DOUBLE WALL)
PLATE SPACER
(RECESSED MOUNT)
2 REQUIRED
BASE PLATE (HOLD DOWN) OR
STARTER PLATE SCREWED
DOWN TO HEADER PLATE
NOTE: THESE PARTS ARE SUPPLIED WITH THE FURNACE
GASKET
HEADER PLATE AND GASKETS
PROVIDED WITH FURNACE
50,000 BTU/hr. MODEL SERIES AND HEADER NOT SHOWN
FLUE COLLAR GASKET NOT REQUIRED ON 500 MODEL SERIES
TAKE CARE NOT TO DISTURB
GASKET GLUED TO THE HEADER
UNDERSIDE. GASKET MAT4RIAL
MUST NOT BLOCK THE FLUE
EXTENSION.
FLUE COLLAR
GASKET
INSTALLING YOUR FURNACE