EasyManua.ls Logo

Crest Audio FBN0751 - Corrective Action

Crest Audio FBN0751
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Troubleshooting
Service Manual
38
Table 3A Troubleshooting Chart - No Display
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 vac supplied to unit. • Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON position.
• Check 120 vac through the ON/OFF switch.
• Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- No voltage through the switch. • Replace switch.
- Bad display board. • Replace board.
- Bad main control board. • Replace the main control board.
- Blown fuse. • Replace fuse F2 on the main control board, see
page 37 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat satisfied. • Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) set point for
main control board.
• Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3C on page 39 of this manual.
- Unit locked out on fault. • Consult display for specific fault. Refer to fault
descriptions on page 41 of this manual for corrective
actions.
Unit Does Not
Modulate
Up to 100%
- Ramp delay active. • Check ramp delay parameter settings. Optional PC
software required.
• Turn ramp delay feature off. See page 20 of this
manual for instructions on how to turn this feature off.
- Boiler controlled by BMS.
• Check BMS parameter settings.