EasyManua.ls Logo

CUTES CT-2004-3A7 - Page 107

Default Icon
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
107
Function Code Table
Code
No.
Function Detail of Data Initial factory
setting
MODBUS
Address
Cd23 Braking mode 0: de-active
1: Active when stop
2: Active when start
3: Active both stop and start
0 151
Cd24 DC braking
frequency
Cd25 DC braking
voltage
1-60HZ 1 152
0-15 5 153
Cd26 DC braking time 1-60 Sec. 1 154
Cd27 Operation
direction setting
Cd28 Restart in
instantaneous
power failure /
Free run start
0: Both forward and reverse
1: Forward only
2: Reverse only
0: Without / Without
1: With / Without
2: Without / With
3: With / With
0 155
0 156
Cd29 Time 1-9000 (Sec.) 5 157
Cd30 “Stop” function at
panel key under
the operation of
external sequence
0: Impossible
1: Possible
1 158
Cd31 Initialize data 0: No change 0
1: Data at the time of shipment
Cd36 Memory clear for
fault annunciation
Cd37 Frequency gain
setting
Cd38 Analog output
calibrate
Cd39 Frequency
command bias
1: Memory clear 0
20-200% 100 165
90-110% 100 166
0-250 125 167