27
Adjust and Function Specification
Item of display
changing
Parameter
▲
selection
▼
Parameter
modification
Press▲,▼ key at display mode, select required item.
Press ▲,▼ key to change value when screen
shows Cd- (General parameter input area) or
CE- (Failure display and engineering mode). Press and
hold ▲,▼ key can progressively increase or
decrease value.
Press ▲,▼ key at parameter input mode can change
parameter. Using with SET key to modify parameter.
Input a number Input a number
0
9
•
D. Function Code
§Cd00 Set frequency (settable range 0.5-240 HZ)
There are 5 methods to change set frequency. Items A~C are methods of panel key
operation, items D-E are methods of external terminal input.
A. At display function, press READ and setting (Cd01=0)
B. Use PROG key to input data (Cd01=0)
C. Use ▼、▲ key to input data (Cd01=0)
D. Use Multi-Step function to setting (Refer to function CE05 to CE55.)
E. Set external voltage
F. Set external current
Note:
1. Set value should be in accordance with V/F slope (Cd05) and upper limit
frequency (Cd17).
Set by function key
A. At display function, press READ and setting (Cd01=0)