Adjust and Function Specification
§Cd15 Jogging frequency (Settable range 0.5-30)
To control jogging, use external terminal 4-FR or 4-RR with COM shorted.
Set running direction
FR
or
RR
2
Running
mode:
Jogging
Forward(Reverse)
Note: Jogging operation is valid only when operation command selects the
external operation signal mode (e.g. Cd04=1) and Cd59=0 or 1.
Jogging operation procedures:
1. First put in 4, and then FR (or RR).
2. Put in 4 and FR (or RR) simultaneously.
Be sure always to put in 4 before FR (or RR).
§Cd16 Start frequency (Settable range 0.5-60)
Set motor start frequency
Settable range of frequency from 0.5Hz to 30Hz, accuracy is 0.01Hz.
Frequency
Start
Frequency
Time
Note: The most appropriate range for start frequency is 0.5Hz to 10Hz.
§ Cd17 Upper limiter of frequency (Selective range 10-240)