Adjust and Function Specification
§Cd18 Lower limiter of frequency (Settable range 0.5-100)
This limiter is used to operate within lower limit frequency of motor
Output
Frequency
Upper
Limiter
Lower
Limiter
FH
Set
Frequency
Operation
§Cd19 Acceleration / deceleration time of jogging (Setting range
0.10-30.00)
Time needed for set frequency from 0Hz to 50Hz.
Set Value (T) = (50 - 0) / F ×T1
T1: Time needed for acceleration/deceleration
F: Frequency changed
§Cd20, 21 Jump frequency (Settable range 0-240)
This function is to avoid mechanical resonance frequency
Frequency operation automatically jumps to point /jump width (set by
Cd22)
This function is only available on constant speed operation, not influence
during acceleration/deceleration, it is settable at 2 points.
Output
Frequency
Cd21
Cd20
Cd22
Cd22
Time
§Cd22 Jump frequency width (Settable range 0-6)