47
Adjust and Function Specification
§Cd31 Initial factory setting (Settable range 0,1)
The function cannot be modified during revolution.
Set data to original factory setting.
Cd31=0 No change
Cd31=1 Initial factory setting, refer to function code table.
Note:
After this function is active, content value returns to “0”, readable value
is always “0”.
§ Cd34 Dead Time compensation delay angle (Settable range 0~80)
Default setting. Can’t be adjustable
Adjust angle of DEATIME compensation in accordance with current feedback
waveform.
§Cd36 Failure record clear (Settable range 0, 1)
Clear the failure record content of Code 32, 33, 34, and 35.
Cd36=0 No change
Cd36=1 All of the contents of data will be “nOnE”, display of “LoAd” after setting
Note: After this function is active, content value automatically returns to “0”, thus
readable value is always “0”.
§Cd37 Frequency gain setting (Settable range 20-200)
Select ratio of frequency gain
Gain setting for external input signals are available using this function.
Output Frequency = Set Value ×Frequency Gain ×MAX. frequency
Ex. Under the mode of external voltage (0-10V) frequency setting,
frequency gain = 100%, set voltage to 2V,MAX. frequency (FH) is 120Hz:
Output Frequency = (2V/10V) ×120Hz ×100% = 24Hz
If change frequency gain to 150%, then
Output Frequency = (2V/10V) ×120Hz ×150% = 36Hz