C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
53
Adjust and Function Specification
§ Cd46 Speed multiplier (Settable range 0.01-500)
The function shows revolution speed multiplied by a scaling factor on the Display.
Note:
1. HZ and A LED de-active.
2. RPM = Frequency ×Cd46
3. If the value overflow, it will show “9999”.
§Cd47 Relay 1 output select (Settable range 0-6)
The function sets the mode of relay1 to activate.
Cd47 Specification Remark
0 Time counter Time reached to the content of Cd29
1 Fault
2 Stop
3 Acceleration
4 Speed reached
5 Deceleration
6 Speed pass over
Revolution frequency >content of Cd45
§Cd48 Relay 1 output select (Settable range 0-6)
The function sets the mode of relay2 to activate.
Cd47 Specification Remark
0 Time counter Time reached to the content of Cd29
1 Fault
2 Stop
3 Acceleration
4 Speed reached
5 Deceleration
6 Speed pass over
Revolution frequency >content of Cd45
§Cd49 Function to lock data (Settable range 0, 1)
To lock data, prevent errors by none operator.
Cd49=0 Data change capable