Adjust and Function Specification
§Cd60 V / F frequency FC (Settable range 0.5-240)
This function cannot be modified during revolution.
To set V/F slope frequency FC when Cd05=11.
Settable range 10Hz-240Hz (FC ≦Fb)
15%
150
Cd7 VB
0%
0
FC Fb FH
Cd60 Cd58 Cd57
(HZ)
Output Frequency
§Cd61 PWN frequency (Settable range 0-4)
This function cannot be modified during revolution.
This function is to set PWM frequency.
The higher pitch of PWM & the lower noise of motor, however motor might be shave.
The lower pitch of PWM & the higher noise of motor, however motor should be more
stable.
Cd61 PWM Frequency
0 Setting by Cd62 (1.5 – 4.0 Hz)
1 4 KHZ
2 6 KHZ
3 8 KHZ
4 10 KHZ
§Cd62 PWM Frequency (Settable range 15-40)
This function cannot be adjusted during operation.
Ex: Cd62 = 15, PWM Frequency = 1.5KHz
Ex: Cd62 = 30, PWM Frequency = 3.0KHz
§Cd63 Switch point for 3
rd
phase PWM and 2
nd
phase PWM(Settable range 5-17)
This function is adjustable during revolution
Ex. Cd63 = 5 when output voltage of inverter exceed rated voltage 5%+3%=8%,
inverter output shift from 3
rd
phase PWM to 2
nd
phase PWM. When output voltage
lower than 5% of rated voltage, inverter output shift from 2
nd
phase PWM to 3
rd
phase PWM.